LiquiFlo 1.5 AC General Purpose (Volts/Hertz) and Vector Duty Drive Software Start-Up and Reference Manual Version 1.
The information in this manual is subject to change without notice. Throughout this manual, the following notes are used to alert you to safety considerations: ! ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Important: Identifies information that is critical for successful application and understanding of the product.
CONTENTS Contents Chapter 1 Using the Start-Up Routines on the LCD OIM 1.1 Preparing for Start-Up ..................................................................................... 1-1 1.2 Running the Start-Up Routines........................................................................ 1-2 Chapter 2 Using the LCD OIM 2.1 Installing and Removing the LCD OIM ............................................................ 2-2 2.1.1 Removing the LCD OIM While the Drive is Powered ......................
5.8 Troubleshooting the Drive Using the LCD OIM..............................................5-19 5.8.1 Accessing the Fault Queue..................................................................5-19 5.8.2 Accessing the Fault Parameters..........................................................5-20 5.8.3 Accessing the Drive Status Parameters ..............................................5-20 5.8.4 Determining the Product Version.........................................................5-21 5.8.
List of Figures Figure 1.1 – Accessing the Start-Up Routines.......................................................... 1-2 Figure 1.2 – Start-Up Menu ...................................................................................... 1-2 Figure 2.1 – LCD OIM............................................................................................... 2-1 Figure 2.2 – Installing and Removing the Local LCD OIM........................................ 2-2 Figure 2.3 – The Display (Main Menu Shown) .........
Figure 4.29 – Anlg In Config (320) ..........................................................................4-68 Figure 4.30 – Anlg in Sqr Root (321) ......................................................................4-68 Figure 4.31 – Analog Out Config.............................................................................4-71 Figure 4.32 – Anlg Out Absolute (341)....................................................................4-72 Figure 5.1 – Location of DC Bus Voltage Measuring Points ......
List of Tables Table 1.1 – Quickstart Parameters ........................................................................... 1-3 Table 2.1 – Key Functions ........................................................................................ 2-4 Table 2.2 – How to Adjust Each Parameter Type..................................................... 2-7 Table 4.1 – Default Values for Preset Speeds 1-7 ................................................. 4-23 Table 4.2 – Analog Output Scaling .......................
VI LiquiFlo 1.5 AC Drive, Software Reference Version 1.
CHAPTER 1 Using the Start-Up Routines on the LCD OIM ! ATTENTION:Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this chapter in its entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.
1.2 Running the Start-Up Routines To access the Start-Up routines, select the Start-Up icon from the main menu as shown in figure 1.1. >> Auto Stopped P0: LiquiFlo 1.5 Main Menu Start-Up Monitor Lang Highlight Start-Up icon Select Figure 1.1 – Accessing the Start-Up Routines The Start-Up menu screen contains 8 selections. The first 7 menu items contain the most commonly used parameters associated with each function. See figure 1.2.
You do not have to configure all of the parameters in all 7 menus. The first menu selection, Quickstart, contains the minimum basic parameters that must be configured before running the drive. These parameters are listed in table 1.1. Table 1.1 – Quickstart Parameters Parameter No.
1-4 LiquiFlo 1.5 AC Drive, Software Reference Version 1.
CHAPTER 2 Using the LCD OIM The LCD Operator Interface Module (OIM) is a keypad/display that enables you to program, monitor, and control the drive. Refer to section 2.3 for the display description. F1 F2 F3 F4 ESC/ PROG Refer to section 2.4 for the key descriptions. tex t HAND o AUTO I Figure 2.
2.1 Installing and Removing the LCD OIM A cable (RECBL-LCD) must be used to convert the OIM for hand-held use. The maximum cable length is 32 feet using extender cables. To install the LCD OIM, connect the OIM to DPI port 3 on the DPI Communication Interface board until it clicks into place. To remove the LCD OIM, pull back on the OIM cable connector to release the OIM from the DPI Communication Interface board.
If the LCD OIM is not the selected control source or reference source, removing the OIM while the drive is powered will have no effect on drive operation. 2.2 Display Description PI ➁ ➄ ➅ ➆ ➃ ➂ Stopped Auto P0: LiquiFlo 1.5 Operational Status Line Device Selected/Error Text Main Menu Menu, Programming Screen, or Process (User) Display Start-Up Lang Function Key Line ➀ ➀ ➁ Function Key (F1, F2, F3, F4) definitions ➂ ➃ ➄ ➅ ➆ PI loop status: PI = PI control is active.
2.2.1 Key Descriptions Table 2.1 – Key Functions Key Function Scroll through options or user function keys, move cursor to the left. Scroll through options or user functions keys, move cursor to the right. Scroll through options, increase a value, or toggle a bit. Scroll through options, decrease a value, or toggle a bit. ESC/ PROG Exit a menu, cancel a change to a parameter, or toggle between program and process (user) display screens.
2.
2.4 Powering Up and Adjusting the LCD OIM The first time the LCD OIM is powered up, you will be prompted to select a language for the display text. If the Start-Up routine has not been completed, the Start-Up menu is displayed immediately following the language selection screen. On subsequent power ups, if both of these requirements have been met, the Main Menu is displayed after the initialization screen. 2.4.
• Parameter range • F1 key defined as a toggle to enable you to view the parameter’s current value and the factory-default value See figure 2.5 and table 2.2 for instructions on how to adjust the parameter values. Step 1. At the parameter entry screen, press to highlight the parameter value. (The screen shown here was accessed using the Parameters>P Numbers path) Step 2. Adjust the parameter value (see table B.2), and then press to save the value.
2.6.2 Loading and Saving User Sets Drive configurations, called user sets, can be saved and recalled for use at any time. Up to three user sets can be saved in the LiquiFlo drive. To save the current drive configuration, select Save to User Set from the Memory Storage menu. To recall, or load, a user set, select Load Frm Usr Set from the Memory Storage menu. To identify which user set is active, select Active User Set from the Memory Storage menu.
2.7.1 Displaying and Changing the OIM Reference You can display the reference value that the OIM is sending to the drive by pressing the up or down arrow key once when the process display screen is active. See figure 2.7. The OIM reference can be used for the speed reference, PI reference, or trim reference. To change the displayed reference, press and hold down either the up or down arrow key until the desired value is displayed. Release the key to return to the process display screen.
2.7.3 Customizing the Function Keys The function keys (F1, F2, F3, and F4, also called F-Keys) on the OIM can be customized to perform several pre-configured functions when the process display screen is active. Up to eight function keys can be configured. Pressing active toggles between each set of four functions. while the display screen is As shipped from the factory, the F4 key is configured for the Clear Fault Queue function.
Select from the list of preconfigured functions: Undefined (default) Load User Set 1-3: Loads the specified user set into active drive memory. The drive responds as if a value had been entered in Load Frm User Set (198), or Load Frm Usr Set was selected from the OIM’s Memory Storage menu. ! ATTENTION:Loading a user set with LevelSense Start (168) set to Enable can result in the drive starting immediately when all start conditions are met.
2.7.3.1 Customizing the Function Key Label Text You can customize the text for each function key label (up to five characters). See figure 2.10. Function List: From figure Undefined Load User Set 1 2.
Auto Stopped 0.00 0.00 0.00 Luse1 Auto Stopped P0: LiquiFlo 1.5 P0: LiquiFlo 1.5 Volts Amps Hz Fltq Normal Video 0.0 0.0 0 0.0 0 0 Volt Amp s Hzs Luse1 Fltq Reverse Video Figure 2.11 – Selecting Reverse Video for the Process Display Screen 2.8 Controlling the Drive From the LCD OIM When the OIM is the selected control source, it can be used to control the drive: • Start (Run) • Stop • Clear Faults 2.8.1 Starting the Drive When the OIM is the selected control source, pressing to the drive.
2-14 LiquiFlo 1.5 AC Drive, Software Reference Version 1.
CHAPTER 3 Programming Basics To program the drive for a specific application, you adjust the appropriate parameters. The parameters are used to define characteristics of the drive. This chapter provides an overview of parameter types and how they are organized. Parameter descriptions are provided in chapter 4. 3.1 About Parameters There are three types of parameters: • Numbered List Parameters Numbered list parameters allow a selection from two or more options.
3.2 How Parameters are Organized Parameters are organized into seven files: • Monitor • Motor Control • Speed Command • Dynamic Control • Utility • Communication • Inputs & Outputs Each file contains parameters that are grouped by their function. A file can contain several groups of parameters. See figure 3.1.
3.3 Accessing the Parameters Parameters are programmed and viewed using the LCD OIM or VS Utilities software. The LCD OIM displays parameters by group, by individual parameter number, and parameters that have changed from their default value. To access parameters using the LCD OIM, select the Parameters icon from the main screen. See figure 3.2. See chapter 2 for information on modifying parameters using the LCD OIM.
3.3.1 Selecting the Parameter Access Level The LiquiFlo 1.5 AC drive provides two levels of access to the parameters: Basic (0) and Advanced (1). The Advanced level allows access to all of the parameters. The Basic level allows access to a subset of the Standard level and contains only the most commonly used parameters. See Appendix B for a list of the parameters available at the Basic level. The active access level is displayed in Parameter Access Level (196).
3.3.2 Restricting Access to Other Parameter Levels ATTENTION:It is the user’s responsibility to determine how to distribute the access level password. Reliance Electric is not responsible for unauthorized access violations within the user’s organization. Failure to observe this precaution could result in bodily injury. ! The LCD OIM provides the option to restrict access to other parameter levels. This feature requires the use of a user-defined password when an attempt to change the access level is made.
3.4 Ensuring Program Security ATTENTION:It is the user’s responsibility to determine how to distribute the write-protect password. Reliance Electric is not responsible for unauthorized access violations within the user’s organization. Failure to observe this precaution could result in bodily injury. ! Parameter values can be password-protected using the LCD OIM. When the password is enabled, parameter values can be displayed.
CHAPTER 4 Parameter Descriptions The following information is provided for each parameter along with its description: Parameter Number: Unique number assigned to each parameter. Parameter Name: Unique name assigned to each parameter. Range: Predefined parameter limits or selections. Note that a negative Hz value indicates reverse rotation. Default: Factory default setting. Access: Parameter access level.
1 Output Freq Range: +/-400.0 Hz [0.1 Hz] Default: Read Only Access: 0 Path: Monitor>Metering See also: The output frequency present at T1, T2, and T3 (U, V, and W). 2 Commanded Freq Range: +/- 400.0 Hz [0.1 Hz] Default: Read Only Access: 0 Path: Monitor>Metering See also: The value of the active frequency command. 3 Output Current Range: 0.0 to Drive Rated Amps x 2 [0.
6 Output Voltage Range: 0.0 to Drive Rated Volts [0.1 VAC] Default: Read Only Access: 1 Path: Monitor>Metering See also: The output voltage present at terminals T1, T2, and T3 (U, V, and W). 7 Output Power Range: 0.0 to Drive Rated kW x 2 [0.1 kW] Default: Read Only Access: 1 Path: Monitor>Metering See also: The output power present at T1, T2, and T3 (U, V, and W). 8 Output Powr Fctr Range: 0.00 to 1.00 [0.
11 MOP Frequency Range: +/- 400.0 Default: Read Only Access: 1 [0.1 Hz] Path: Monitor>Metering See also: The value of the signal at the MOP (Motor-Operated Potentiometer). 12 DC Bus Voltage Range: Based on drive rating [0.1 VDC] Default: Read Only Access: 0 Path: Monitor>Metering See also: The present DC bus voltage level. 13 DC Bus Memory Range: Based on drive rating [0.
21 Ground Current Range: 0.0 to 3276.7 [0.1 A] Default: Read Only Access: 1 Path: Monitor>Metering See also: The analog value of ground current on A/D channel 5. 22 23 24 Phase U Amps Phase V Amps Phase W Amps Range: 0.0 to 3276.7 [0.1 A] Default: Read Only Access: 1 Path: Monitor>Metering See also: The RMS motor current value, as follows: • Parameter 22 displays the phase U current value. • Parameter 23 displays the phase V current value. • Parameter 24 displays the phase W current value.
27 Rated Volts Range: 208 to 480 V [0.1 VAC] Default: Read Only Access: 1 Path: Monitor>Drive Data See also: The drive input voltage class (208, 240, 400, etc.). 28 Rated Amps Range: 0.0 to 6553.5 Amps [0.1 Amps] Default: Read Only Access: 1 Path: Monitor>Drive Data See also: The drive rated output current. 29 Control SW Ver Range: 0.000 to 65.256 [0.001] Default: Read Only Access: 1 See also: 196 Path: Monitor>Drive Data The Main Control board software version.
31 Appl Analog Output Range: 4.000 to 20.000 [0.001 A] Default: 4.000 Access: 1 See also: 196 Path: Monitor>Application This parameter is not used with LiquiFlo 1.5 AC drives. The data output on the analog output when configured for “Application” control. 32 Rectifier Config Range: 0 = Run at Start 1 = Run at Power Up 2 = Manual Control 3 = No Rectifier Default: 3 Access: 1 See also: 196 Path: Monitor>Application This parameter is not used with LiquiFlo 1.5 AC drives.
33 Rectifier Control Range: See figure 4.2 Default: Read Only Access: 1 Path: Monitor>Application See also: Ma n Ma ual E nu na al C ble los Re e P ctif re- ier AC cha Lin nrg AC e e Lin I/O: AC e Di I g / AC Line O: Di . Out Lin I/O: g. O put AC e I Di ut 6 L /O g pu AC ine : Dig. Out t 5 Lin I/O: . O put e I Dig utp 4 /O: . O ut Dig utp 3 . O ut utp 2 ut 1 This parameter is not used with LiquiFlo 1.5 AC drives. The commanded state of the rectifier.
35 Rectifier Fault Range: 0 to 299 Default: Read Only Access: 1 Path: Monitor>Application See also: This parameter is not used with LiquiFlo 1.5 AC drives. Displays a fault from the rectifier. 40 Motor Type Range: 0 = Induction 1 = Synchr Reluc 2 = Synchr PM Default: 0 = Induction Access: 1 Path: Motor Control>Motor Data See also: Set to match the type of motor connected; Induction, Synchronous Reluctance, or Synchronous Permanent Magnet. 41 Motor NP Volts Range: 0.
43 Motor NP Hertz Range: 5.0 to 250.0 Hz [0.1 Hz] Default: Based on Drive Type Access: 0 Path: Motor Control>Motor Data See also: Set to the motor nameplate rated frequency. The motor nameplate base frequency defines the output frequency when operating at rated voltage, rated current, rated speed, and rated temperature. 44 Motor NP RPM Range: 60 to 24000 RPM [1 RPM] Default: 1750 RPM Access: 0 Path: Motor Control>Motor Data See also: Set to the motor nameplate rated RPM.
47 Motor OL Hertz Range: 0.0 to Motor NP Hz [0.1 Hz] Default: 0 Access: 0 See also: 42, 220 Path: Motor Control>Motor Data Selects the output frequency below which the motor operating current is derated. The motor thermal overload will generate a fault at lower levels of current. For all settings of overload Hz other than zero, the overload capacity is reduced to 70% when output frequency is zero. 48 Motor Overload Amps Range: 1.0 to 2000.0 [0.
53 Torque Perf Mode Range: 0 = Sensrls Vect 1 = SV Economize 2 = Custom V/Hz 3 = Fan/Pmp-V/Hz Default: 0 = Sensrls Vect Access: 0 See also: 62, 63, 69, 70 Path: Motor Control>Torq Attributes Sets the method of motor torque production. 54 Maximum Voltage Range: (Rated Volts x 0.25) to Rated Volts [0.1 VAC] Default: Drive Rated Volts Access: 0 Path: Motor Control>Torq Attributes See also: Sets the highest voltage the drive will output. 55 Maximum Freq Range: 5.0 to 250.0 Hz [0.
56 Compensation Range: See figure 4.5 Default: See figure 4.5 Access: 1 Path: Motor Control>Torq Attributes See also: Ixo A En utoC ab al Re le J c flec erk tW ave Enables/disables the compensation correction options. x x x x x x x x x x x x x 0 1 1 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Nibble 4 Nibble 3 Nibble 2 Nibble 1 Bit # Factory Default Bit Values 1 =Enabled 0 =Disabled x =Reserved Figure 4.
58 Flux Up Time Range: 0.00 to 5.00 sec [0.01 sec] Default: 0.0 sec Access: 1 See also: 53, 58 Path: Motor Control>Torq Attributes Sets the amount of time the drive will use to try to achieve full motor stator flux. When a start command is issued, DC current at current limit level is used to build stator flux before accelerating.
! ATTENTION: Rotation of the motor in an undesired direction can occur during this procedure (Autotune (61) = Rotate Tune (2)). To guard against possible injury and/or equipment damage, it is recommended that the motor be disconnected from the load before proceeding. Important: Rotate Tune (2) is used when motor is uncoupled from the load. Results may not be valid if a load is coupled to the motor during this procedure.
69 Start/Acc Boost Range: 0.0 to Motor NP Volts x 0.25 [0.1 VAC] Default: Based on drive rating Access: 1 See also: 53, 70, 83 Path: Motor Control>Volts per Hertz Sets the voltage boost level for starting and acceleration when Custom V/Hz mode is selected in Torque Perf Mode (53). 70 Run Boost Range: 0.0 to Motor NP Volts x 0.25 [0.
81 Minimum Speed Range: 0.0 to Maximum Speed [0.1 Hz] Default: 0.0 Hz Access: 0 See also: 83, 92, 95 Path: Speed Command>Spd Mode & Limits Sets the low limit for the speed reference after scaling is applied. ! 82 ATTENTION: The drive can operate at and maintain zero speed.
83 Overspeed Limit Range: 0.0 to 20.0 Hz [0.1 Hz] Default: 10.0 Hz Access: 1 See also: 55, 82 Path: Speed Command>Spd Mode & Limits Sets the incremental amount of the output frequency (above Maximum Speed) allowable for functions such as slip compensation. See figure 4.
87 Skip Freq Band Range: 0.0 to 30.0 Hz [0.1 Hz] Default: 0.0 Hz Access: 1 See also: 84, 85, 86 Path: Speed Command>Spd Mode & Limits Determines the bandwidth around a skip frequency (half the band above and half the band below the skip frequency).
91 Speed Ref A Hi Range: -/+Maximum Speed [0.1 Hz] Default: Maximum Speed Access: 0 See also: 82 Path: Speed Command>Speed References Scales the upper value of the Speed Ref A Sel (90) selection when the source is an analog input. 92 Speed Ref A Lo Range: -/+Maximum Speed [0.1 Hz] Default: 0.0 Hz Access: 0 Path: Speed Command>Speed References See also: 81 Scales the lower value of the Speed Ref A Sel (90) selection when the source is an analog input.
! 94 ATTENTION: Removing and replacing the LCD OIM while the drive is running may cause an abrupt speed change if the LCD OIM is the selected reference source, but is not the selected control source. The drive will ramp to the reference level provided by the OIM at the rate specified in Accel Time 1 (140), Accel Time 2 (141), Decel Time 1 (142) and Decel Time 2 (143). Be aware that an abrupt speed change may occur depending upon the new reference level and the rate specified in these parameters.
97 TB Man Ref Hi Range: -/+Maximum Speed [0.1 Hz] Default: Maximum Speed Access: 0 Path: Speed Command>Speed References See also: 96 Scales the upper value of the TB Man Ref Sel selection when the source is an analog input. 98 TB Man Ref Lo Range: -/+Maximum Speed [0.1 Hz] Default: 0.0 Hz Access: 0 See also: 96 Path: Speed Command>Speed References Scales the lower value of the TB Man Ref Sel selection when the source is an analog input. 100 Jog Speed Range: 0 to Maximum Speed [0.
Table 4.1 – Default Values for Preset Speeds 1-7 117 Parameter No. Parameter Name Default 101 Preset Speed 1 5.0 Hz 102 Preset Speed 2 10.0 Hz 103 Preset Speed 3 20.0 Hz 104 Preset Speed 4 30.0 Hz 105 Preset Speed 5 40.0 Hz 106 Preset Speed 6 50.0 Hz 107 Preset Speed 7 60.
Trim Trim Ref Re B fA x x x x x x x x x x x x x x 0 0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Nibble 4 Nibble 3 Nibble 2 Nibble 1 Bit # Factory Default Bit Values 1 =Trimmed 0 =Not Trimmed x =Reserved Figure 4.7 – Trim Out Select (118) 119 Trim Hi Range: -/+Maximum Speed [0.1 Hz] Default: 60.0 Hz Access: 1 See also: 82, 117 Path: Speed Command>Speed Trim Scales the upper value of the Trim In Select (117) selection when the source is an analog input. 120 Trim Lo Range: -/+Maximum Speed [0.
122 Slip Comp Gain Range: 1.0 to 100.0 [0.1] Default: 40.0 Access: 1 See also: 80, 121, 122 Path: Speed Command>Slip Comp Sets the response time of slip compensation. 123 Slip RPM Meter Range: 0.0 to 300.0 RPM Default: Read Only Access: 1 See also: 80, 121, 122 Path: Speed Command>Slip Comp Displays the present amount of adjustment being applied as slip compensation. 124 PI Configuration Range: See figure 4.8 Default: See figure 4.
Bit 2 - Preload Mode • Enabled = Initializes the PI integrator to the commanded speed while the PI is disabled. • Disabled = The PI integrator is loaded with the PI Pre-load (133) while the PI is disabled. Bit 3 - Ramp Ref • Enables/disables ramping the reference used from PI Feedback to the selected PI Reference. Bit 4 - Zero Clamp • Enables/disables option to limit operation so that the output frequency always has the same sign as the master speed reference.
PI R PI eset H PI old En ab le x x x x x x x x x x x x x 0 0 0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Nibble 4 Nibble 3 Nibble 2 Nibble 1 Bit # Factory Default Bit Values 1 =Enabled 0 =Disabled x =Reserved Figure 4.9 – PI Control (125) Bit 0 - PI Enable • Enables/disables the operation of the PI loop. Bit 1 - PI Hold • Enabled = The integrator for the outer control loop is held at the current level; that is, it will not increase.
127 PI Setpoint Range: -/+100.00% of Maximum Process Value [0.01%] Default: 50.00% Access: 1 See also: 124-138 Path: Speed Command>Process PI Provides an internal fixed value for the process setpoint when PI Reference Sel (126) is set to PI Setpoint.
130 PI Prop Gain Range: 0.00 to 100.00 [0.01] Default: 1.00 Access: 1 See also: 124-138 Path: Speed Command>Process PI Sets the value for the PI proportional component when the PI Hold bit of PI Control (125) = Enabled (1). PI Error x PI Prop Gain = PI Output 131 PI Lower Limit Range: -/+Maximum Frequency [0.1 Hz] Default: -Maximum Freq Access: 1 See also: 124-138 Path: Speed Command>Process PI Sets the lower limit of the PI output.
d PI In PI Limi R t PI eset H PI old En ab le x x x x x x x x x x x x 0 0 0 0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Nibble 4 Nibble 3 Nibble 2 Nibble 1 Bit # 1 =Condition True 0 =Condition False x =Reserved Figure 4.10 – PI Status (134) Bit 0 - PI Enabled • Indicates whether or not the PI loop is enabled. Bit 1 - PI Hold • Is set to 1 to indicate when a digital input is configured for PI Hold and is turned on, or the PI Hold bit is set in PI Control (125).
137 PI Error Meter Range: -/+100.00% [0.01%] Default: Read Only Access: 1 Path: Speed Command>Process PI See also: 124-138 Present value of the PI error signal. 138 PI Output Meter Range: -/+Maximum Freq [0.1 Hz] Default: Read Only Access: 1 See also: 124-138 Path: Speed Command>Process PI Present value of the PI output signal. 140 141 Accel Time 1 Accel Time 2 Range: 0.1 to 100.0 [0.1 sec] Default: 10.
142 143 Decel Time 1 Decel Time 2 Range: 0.1 to 100.0 sec [0.1 sec] Default: 10.0 sec Access: 142=0 143=0 See also: 142, 143, 146, 361-366 Path: Dynamic Control>Ramp Rates Sets the rate of deceleration for all speed decreases. Max Speed / Decel Time = Decel Rate Two decel times exist to enable deceleration rate changes “on the fly” using a building automation system command, digital input, or F-Key on the LCD OIM, if configured (see chapter 2).
149 Current Lmt Gain Range: 0 to 5000 Default: 200 Access: 1 See also: 147, 148 [1] Path: Dynamic Control>Load Limits Sets the responsiveness of the current limit. 150 Drive OL Mode Range: 0 = Disabled 1 = Reduce CLim 2 = Reduce PWM 3 = Both-PWM 1st Default: 0 = Disabled Access: 1 See also: 219 Path: Dynamic Control>Load Limits Selects the drive’s response to increasing drive temperature.
! 157 ATTENTION: The user must provide an external, hardwired emergency stop circuit outside of the drive circuitry. This circuit must disable the system in case of improper operation. Uncontrolled machine operation may result if this procedure is not followed. Failure to observe this precaution could result in bodily injury.
160 Bus Reg Gain Range: 0 to 5000 [1] Default: 450 Access: 1 See also: 161, 162 Path: Dynamic Control>Stop/Brake Modes Sets the responsiveness of the bus regulator. 161 162 Bus Reg Mode A Bus Reg Mode B Range: 0 = Disabled 1 = Adjust Freq 2 = Dynamic Brak 3 = Both - DB 1st 4 = Both - Frq 1st Default: Mode A: 0 = Disabled Mode B: 0 = Disabled Access: 0 See also: 160, 163, 361-366 Path: Dynamic Control>Stop/Brake Modes Sets the method and sequence of the DC bus regulator voltage.
! ATTENTION: The adjust freq portion of the bus regulator function is extremely useful for preventing nuisance overvoltage faults resulting from aggressive decelerations, overhauling loads, and eccentric loads. It forces the output frequency to be greater than commanded frequency while the drive’s bus voltage is increasing towards levels that would otherwise cause a fault.
165 Bus Reg Kd Range: 0 to 10000 Default: 1000 Access: 1 Path: Dynamic Control>Stop/Brake Modes See also: Derivative gain for the bus regulator. Used to control regulator overshoot. 168 Start At PowerUp Range: 0 = Disabled Default: 0 = Disabled Access: 0 Path: Dynamic Control>Stop/Restart Modes See also: This parameter is not used with LiquiFlo AC drives.
174 Auto Rstrt Tries Range: 0 to 9 [1] Default: 0 (Disabled) Access: 0 See also: 175 ! Path: Dynamic Control>Restart Modes ATTENTION: Equipment damage and/or personal injury may result if parameter 174 is used in an inappropriate application. Do not use this function without considering applicable local, national, and international codes, standards, regulations, or industry guidelines.
• Setting Auto Restrt Tries to zero. • Occurrence of a fault that is not auto-resettable. • Removing power from the drive. • Exhausting an auto-reset/run cycle. Note that two autotuning status bits are provided in Drive Status 2 (210): an active status bit and a countdown status bit. 175 Auto Rstrt Delay Range: 0.5 to 30.0 sec Default: 1.0 sec Access: 0 See also: 174 [0.1 sec] Path: Dynamic Control>Restart Modes Sets the time between restart attempts when the auto restart feature is enabled.
181 Wake Time Range: 0.0 to 30.0 [0.1 sec] Default: 1.0 Access: 1 See also: 180 Path: Dynamic Control>Restart Modes Defines the amount of time at or above Wake Level before a start command is issued. This parameter is not used with LiquiFlo AC drives. 182 Sleep Level Range: 4.000 mA, 0.000 V / Wake Level [0.001 mA, 0.001 V] Default: 5.000 mA, 5.000 V Access: 1 See also: 183 Path: Dynamic Control>Restart Modes Defines the analog input level that will stop the drive.
185 Power Loss Time Range: 0.0 to 60.0 sec [0.1 sec] Default: 0.5 sec Access: 0 See also: 184 Path: Dynamic Control>Power Loss Sets the time that the drive will remain in power loss mode before a fault is issued. 186 Power Loss Level Range: 0.0 to 99.9 [0.1 VDC] Default: Drive Rated Volts Access: 1 See also: 184 Path: Dynamic Control>Power Loss Sets the level at which the Power Loss Mode selection will occur.
192 Save OIM Ref Range: See figure 4.11 Default: See figure 4.11 Access: 1 Path: Utility>OIM Ref Config See also: At Po wr Do wn Enables a feature to save the present frequency reference value issued by the OIM to drive memory on power loss. Value is restored to the OIM on power up. x x x x x x x x x x x x x x x 1 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Nibble 4 Nibble 3 Nibble 2 Nibble 1 Bit # Factory Default Bit Values 1 =Save 0 =Do Not Save x =Reserved Figure 4.
ow n At S At top Po wr D x x x x x x x x x x x x x x 0 0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Nibble 4 Nibble 3 Nibble 2 Nibble 1 Bit # Factory Default Bit Values 1 =Save 0 =Do Not Save x =Reserved Figure 4.12 – Save MOP Ref (194) 195 MOP Rate Range: 0.2 to 250.0 Default: 1.0 Hz/sec Access: 1 [0.1 Hz/sec] Path: Utility>MOP Config See also: Sets the rate of change of the MOP reference in response to a digital input.
198 Load Frm Usr Set Range: 0 = Ready 1 = User Set 1 2 = User Set 2 3 = User Set 3 Default: 0 = Ready Access: 0 See also: 199 Path: Utility>Drive Memory Loads a previously saved set of parameter values from a selected user set location in drive non-volatile memory to active drive memory. An F-Key on the LCD OIM can be configured for this function. Refer to chapter 2.
202 Voltage Class Range: 2 = Low Voltage 3 = High Voltage Default: Based on Drive Type Access: 1 See also: 55 Path: Utility>Drive Memory Resets selected parameters that change the drive voltage rating, current rating, scaling, and motor data. Maximum Frequency (55) will be affected by changing this parameter.
209 Drive Status 1 Range: See figure 4.13 Default: Read Only Access: 1 Path: Utility>Diagnostics See also: 210 Sp d Sp Ref d ID Sp Ref 3 (2) d ID Sp Ref 2 (2) d ID Lo Ref 1 (2) ca ID Lo l ID 0 (2) ca 2 ( 1 Lo l ID ) ca 1 ( 1 At l ID ) S 0 (1 Fa peed ) ul Ala ted r De m ce Ac lera ce ti Ac lera ng tua tin Co l D g m ir Ac man tiv d Re e Dir ad y Present operating condition of the drive.
210 Drive Status 2 Range: See figure 4.14 Default: Read Only Access: 1 See also: 209 Path: Utility>Diagnostics DP I Mo at 50 t 0 Bu or Ov k s F er Cu req ld rr R Au Lim eg toR it Au st toR Act st C tdn Au toT DC uni n Sto Brak g i p n Jog ping g Ru ging n Ac ning tive Re ad y Present operating condition of the drive. x x 1 0 1 1 1 0 x 0 0 0 1 1 0 0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Nibble 4 Nibble 3 Nibble 2 Nibble 1 Bit # 1 =Condition True 0 =Condition False x =Reserved Figure 4.
211 Drive Alarm 1 Range: See figure 4.15 Default: Read Only Access: 1 See also: 212, 259 Path: Utility>Diagnostics Utility>Alarms Indicates Type 1 alarm conditions that currently exist in the drive. Note that for alarm conditions not configured in Alarm Config 1 (259), the status indicated will be a zero.
213 Speed Ref Source Range: 0 = PI Output 1 = Analog In 1 2 = Analog In 2 3-8 = Reserved 9 = MOP Level 10 = Jog Speed 11 = Preset Spd 1 12 = Preset Spd 2 13 = Preset Spd 3 14 = Preset Spd 4 15 = Preset Spd 5 16 = Preset Spd 6 17 = Preset Spd 7 18 = Network 19 = DPI Port 2 20 = DPI Port 3 21 = DPI Port 4 22 = DPI Port 5 23 = Reserved Default: Read Only Access: 1 See also: 90, 93, 96, 101 Path: Utility>Diagnostics Displays the source of the speed reference of the drive.
215 Last Stop Source Range: 0 = Pwr Removed 1 = Network 2 = DPI Port 2 3 = DPI Port 3 4 = DPI Port 4 5 = DPI Port 5 6 = Reserved 7 = Digital In 8 = Fault 9 = Not Enabled 10 = Sleep 11 = Jog Default: Read Only Access: 1 Path: Utility>Diagnostics See also: Displays the source that initiated the most recent stop sequence. It will be cleared (set to 0) during the next start sequence. 216 Dig In Status Range: See figure 4.
Dig i Dig tal O ital ut2 Ou t1 x x x x x x x x x x x x x x 0 0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Nibble 4 Nibble 3 Nibble 2 Nibble 1 Bit # 1 =Output Energized 0 =Output De-energized x =Reserved Figure 4.19 – Dig Out Status (276) 218 Drive Temp Range: -/+100 degC [0.1 degC] Default: Read Only Access: 1 Path: Utility>Diagnostics See also: Present operating temperature of the drive power section. 219 Drive OL Count Range: 0.0 to 100.0% [0.
221 Imbalance Display Range: 0.0 to 100.0 [1.0 %] Default: Read Only Access: 1 See also: 49, 50 Path: Utility>Diagnostics Displays the imbalace in current between motor phases. 224 Fault Frequency Range: 0.0 to +/-400.0 Hz [0.1 Hz] Default: Read Only Access: 1 See also: 225-230 Path: Utility>Diagnostics Captures and displays the output frequency of the drive at the time of the last fault. 225 Fault Amps Range: 0.0 to Rated Amps x 2 [0.
227 Status 1 @ Fault Range: See figure 4.20 Default: Read Only Access: 1 See also: 209, 224-230 Path: Utility>Diagnostics Sp d Sp Ref d ID Sp Ref 3 d ID Sp Ref 2 d ID Lo Ref 1 cal ID Lo ID 0 ca 2 Lo l ID ca 1 At l ID S 0 Fa peed ulte Ala d r De m cel Ac era c ti Ac elera ng tua tin Co l D g m ir Ac man tive d D Re ir ad y Captures and displays Drive Status 1 bit pattern at the time of the last fault.
229 Alarm 1 @ Fault Range: See figure 4.22 Default: Read Only Access: 1 See also: 211, 224-230 Path: Utility>Diagnostics Wa k De ing cel Dr Inh v i Dr OL L bit v O vl LL 2 vl 1 Int DB An Re lg i s O nL H oss Po we Un r Lo d s Pre erVo s l chr tag gA e ctv Captures and displays Drive Alarm 1 at the time of the last fault. x x x x x 0 0 0 0 x 0 0 x 0 0 0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Nibble 4 Nibble 3 Nibble 2 Nibble 1 Bit # 1 =Condition True 0 =Condition False x =Reserved Figure 4.
234 Testpoint 1 Sel Range: 0 to 65535 [1] Default: 499 Access: 1 See also: 235 Path: Utility>Diagnostics Selects the function whose value is displayed in Testpoint 1 Data (235). These are internal values that are not accessible through parameters. See Testpoint Codes and Functions in chapter 5 for a list of codes and functions.
238 Fault Config 1 Range: See figure 4.24 Default: See figure 4.24 Access: 0 Path: Utility>Faults See also: De c Au el Inh tRs ib Sh t Tr it e ie Mo ar Pi s tor n Ov erL Un d de r Po Vo we ltag rL e oss Enables/disables annunciation of the faults shown in figure 4.24. x x x x x x x x x 0 0 0 1 x 1 0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Nibble 4 Nibble 3 Nibble 2 Nibble 1 Bit # 1 =Enabled 0 =Disabled x =Reserved Figure 4.
243 245 247 249 251 253 255 257 Fault 1 Code Fault 2 Code Fault 3 Code Fault 4 Code Fault 5 Code Fault 6 Code Fault 7 Code Fault 8 Code Range: 0000 to 9999 Default: Read Only Access: 1 Path: Utility>Faults See also: A code that represents a drive fault. The codes will appear in these parameters in the order they occur. Fault 1 Code = the most recent fault.
259 Alarm Config 1 Range: See figure 4.25 Default: See figure 4.25 Access: 1 Path: Utility>Alarms See also: Wa k De ing cel Dr inh v i Dr OL L bit v O vl LL 2 vl 1 Int DB An Re lg i s O nL H oss Po we U n r Lo d s Pre erVo s chr ltag gA e ctv Selects alarm conditions that will initiate a drive alarm. Refer to chapter 5, Troubleshooting the Drive, for more information about alarms.
270 DPI Baud Rate Range: 0 = 125 kbps 1 = 500 kbps Default: 1 Access: 1 Path: Communication>Comm Control See also: Sets the baud rate for attached drive peripherals. When changing this value, the drive must be reset for the change to take effect 271 Drive Logic Rslt Range: See figure 4.
272 Drive Ref Rslt Range: 0 to 32767 [1] Default: Read Only Access: 1 Path: Communication>Comm Control See also: Present frequency reference scaled as a DPI reference for peer-to-peer communications. The value shown is the output prior to the accel/decel ramp and any corrections supplied by slip comp, PI, etc.
277 Start Mask Range: See Logic Mask (276) Default: See Logic Mask (276) Access: 1 See also: 288 - 297 Path: Communication>Masks & Owners Controls which modules can issue start commands. 278 Jog Mask Range: See Logic Mask (276) Default: See Logic Mask (276) Access: 1 See also: 288 - 297 Path: Communication>Masks & Owners Controls which modules can issue jog commands.
282 Decel Mask Range: See Logic Mask (276) Default: See Logic Mask (276) Access: 1 See also: 288 - 297 Path: Communication>Masks & Owners Controls which modules can select Decel Time 1, 2. (142, 143) 283 Fault Clr Mask Range: See Logic Mask (276) Default: See Logic Mask (276) Access: 1 See also: 288 - 297 Path: Communication>Masks & Owners Controls which modules can clear a fault.
288 Stop Owner Range: See figure 4.28 Default: Read Only Access: 1 Path: Communication>Masks & Owners See also: 276 - 285 Re s DP erved I DP Port IP 5 DP ort 4 I DP Port IP 3 DP ort 2 I Dig Port 1 ital In Modules that are presently issuing a valid stop command. x x x x x x x x x x 0 0 0 0 0 1 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Nibble 4 Nibble 3 Nibble 2 Nibble 1 Bit # 1 =Issuing Command 0 =No Command x =Reserved Figure 4.
292 Reference Owner Range: See Stop Owner (288) Default: Read Only Access: 1 See also: 276 - 285 Path: Communication>Masks & Owners Adapter that currently has exclusive control of the command frequency source selection. 293 Accel Owner Range: See Stop Owner (288) Default: Read Only Access: 1 See also: 276 - 285 Path: Communication>Masks & Owners Adapter that currently has exclusive control of selecting Accel Time 1, 2.
297 Local Owner Range: See Stop Owner (288) Default: Read Only Access: 1 See also: 276 - 285 Path: Communication>Masks & Owners Adapter that has requested exclusive control of drive logic functions. If an adapter is in local lockout, all other functions (except stop) on all other modules are locked out and non-functional. Local control can be obtained only when the drive is stopped.
. 304 305 Data In C1 - Link C Word 1 Data In C2 - Link C Word 2 Range: 0 to 387 [1] Default: 0 (Disabled) Access: 1 Path: Communication>Datalinks See also: Parameter number whose value will be written from a communications device data table. Parameters that can be changed only while the drive is stopped cannot be used as Datalink inputs. Entering a parameter of this type will disable the link. Refer to the appropriate communications option board manual for datalink information.
312 313 Data Out B1- Link B Word 1 Data Out B2 - Link B Word 2 Range: 0 to 387 [1] Default: 0 (Disabled) Access: 1 Path: Communication>Datalinks See also: Parameter number whose value will be written to a communications device data table. 314 315 Data Out C1- Link C Word 1 Data Out C2 - Link C Word 2 Range: 0 to 387 [1] Default: 0 (Disabled) Access: 1 Path: Communication>Datalinks See also: Parameter number whose value will be written to a communications device data table.
320 Anlg In Config Range: See figure 4.29 Default: See figure 4.29 Access: 0 See also: 322, 323, 325, 326 Path: Inputs & Outputs>Analog Inputs An a An log In alo 2 gI n1 Selects the type of input signal being used for analog input 1 and 2. x x x x x x x x x x x x x x 0 1 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Nibble 4 Nibble 3 Nibble 2 Nibble 1 Bit # Factory Default Bit Values 1 =Current 0 =Voltage x =Reserved Figure 4.29 – Anlg In Config (320) 321 Anlg In Sqr Root Range: See figure 4.
322 Analog In 1 Hi Range: 4.000 to 20.000 mA [0.001 mA] -/+10.000 V [0.1 V] 0.0 to 10.000 V [0.1 V] Default: 20.000 mA Access: 0 See also: 91, 92 Path: Inputs & Outputs>Analog Inputs The drive scales the value read from the analog input and converts it to units usable for the application. The user controls the scaling by setting parameters that associate a low and high point in the input range with a low and high point in the target range.
324 Analog In 1 Loss Range: 0 = Disabled 1 = Fault 2 = Hold Input (use last frequency command) 3 = Set Input Lo (use Minimum Speed as frequency command) 4 = Set Input Hi (use Maximum Speed as frequency command) 5 = Goto Preset1 (use Preset 1 as frequency command) 6 = Hold OutFreq (maintain last output frequency) Default: 0 = Disabled Access: 1 See also: 91, 92 Path: Inputs & Outputs>Analog Inputs Selects drive response when an analog signal loss is detected. (1.6V = signal loss, 1.
327 Analog In 2 Loss Range: 0 = Disabled 1 = Fault 2 = Hold Input (use last frequency command) 3 = Set Input Lo (use Minimum Speed as frequency command) 4 = Set Input Hi (use Maximum Speed as frequency command) 5 = Goto Preset1 (use Preset1 as frequency command) 6 = Hold OutFreq (maintain last output frequency) Default: 0 = Disabled Access: 1 Path: Inputs & Outputs>Analog Inputs See also: 91, 92 Selects drive action when an analog signal loss is detected. (1.6V = signal loss, 1.
341 Anlg Out Absolut Range: See figure 4.32 Default: See figure 4.32 Access: 1 See also: 342 Path: Inputs & Outputs>Analog Outputs An alo gO ut1 Selects whether the signed value or absolute value of a parameter is used before being scaled to drive the analog output. x x x x x x x x x x x x x x x 0 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Nibble 4 Nibble 3 Nibble 2 Nibble 1 Bit # Factory Default Bit Values 1 =Enabled 0 =Disabled x =Reserved Figure 4.
343 Analog Out Scale Hi Range: 0.0 to 20.0 mA / 0.0 to 10.0 V [0.1 mA / 0.1 V] Default: 20.0 mA / 10.0 Volts Access: 0 See also: 342 Path: Inputs & Outputs>Analog Outputs Sets the analog output value when the source value is at maximum. Scaling the Analog Output The user defines the scaling for the analog output by entering analog output voltages into Analog Out1 Lo and Analog Out1 Hi.
361 362 363 364 365 366 Digital In1 Sel Digital In2 Sel Digital In3 Sel Digital In4 Sel Digital In5 Sel Digital In6 Sel Range: 0 = Not Used 1 = Enable 2 = Clear Faults1 3 =Aux Fault4 = Stop - CF2 5 = Start 6 = Fwd/Reverse2 7 = Run3 8 = Run Forward3 9 = Run Reverse3 10 = Jog 11 = Jog Forward 12 = Jog Reverse 13 = Stop Mode B 14 = Bus Reg Md B 15 = Speed Sel 14 16 = Speed Sel 24 17 = Speed Sel 34 18 = Auto/Manual 19 =Local 20 = Acc2 & Dec2 21 = Accel 2 22 = Decel 2 23 = MOP Inc 24 = MOP Dec 25 = Exc Link 26
Table 4.3 – Speed Select Inputs Speed Select Inputs 3 2 1 Reference Source 0 0 0 Speed Ref A Sel 0 0 1 Preset Speed 1 0 1 0 Preset Speed 2 0 1 1 Preset Speed 3 1 0 0 Preset Speed 4 1 0 1 Preset Speed 5 1 1 0 Preset Speed 6 1 1 1 Preset Speed 7 Assigns an input function to the drive’s digital inputs. Note that digital inputs Run, Jog, Clear-Faults, and Direction control functions are operational only when the mask paramters are set fo these functions. Table 4.
4 = Stop - CF (Stop - Clear Faults): An open input will always assert a stop command. While the stop is asserted, the drive ready status will be off. A closed input will allow the drive to start. An open-to-closed transition is interpreted as a clear faults request. The drive will clear any existing faults. If Start is configured, then Stop-Clear Faults must also be configured to prevent a digital input configuration alarm condition. Stop-Clear Faults is optional in all other circumstances.
Table 4.5 – Drive Response to Jog Forward and Jog Reverse Inputs Jog Forward Jog Reverse Open Open Open Closed Closed Open Closed Closed ! Drive Response Drive will stop if already jogging, but can be started by other means. Drive jogs in reverse direction. Drive jogs in forward direction. Drive continues to jog in current direction. ATTENTION: If a normal drive start command is received while the drive is jogging, the drive will switch from jog mode to run mode.
The Speed Select input function configuration process involves assigning the functionality of the three possible Speed Select input functions to physical digital inputs. The three Speed Select inputs functions are called Speed Select 1, Speed Select 2, and Speed Select 3, and they are assigned to physical inputs using the Digital In”x” Sel parameters. Table 4.6 on page 78 describes the various reference sources that can be selected using all three of the Speed Select input functions.
23, 24 = MOP Increment, MOP Decrement: The MOP is a reference setpoint (called the MOP Value) that can be incremented and decremented by external devices. These inputs are used to increment and decrement the Motor Operated Potentiometer (MOP) value inside the drive. The MOP value will be retained through a power cycle. While the MOP Increment input is closed, the MOP value will increase at rate contained in MOP Rate. Units for rate are Hz per second.
380 Digital Out1 Sel Range: 1 = Fault 2 = Alarm 3 = Ready 4 = Run 5 = Forward Run 6 = Reverse Run 7 = Auto Restart 8 = Powerup Run 9 = At Speed 10 = At Freq 11 = At Current 12 = At Torque 13 = At Temp 14 = At Bus Volts 15 = At PI Error 16 = DC Braking 17 = Curr Limit 18 = Economize 19 = Motor Overld 20 = Power Loss 21 = Input 1 Link 22 = Input 2 Link 23 = Input 3 Link 24 = Input 4 Link 25 = Input 5 Link 26 = Input 6 Link 27 = Shunt Trip 28 = Aux Run Default: 1 = Fault Access: 0 See also: 1-4, 12, 48
382 Dig Out1 OnTime Range: 0.00 to 600.00 sec [0.01 sec] Default: 0.00 sec Access: 1 See also: 380 Path: Inputs & Outputs>Digital Outputs Sets the on delay time for the digital outputs. This is the time between the occurrence of a condition and activation of the relay. 383 Dig Out1 OffTime Range: 0.00 to 600.00 sec [0.01 sec] Default: 0.00 sec Access: 1 See also: 380 Path: Inputs & Outputs>Digital Outputs Sets the off delay time for the digital outputs.
385 Dig Out2 Level Range: 0.0 to 819.2 [0.1] Default: 0.0 Access: 0 Path: Inputs & Output>Digital Outputs See also: 384 Sets the relay activation level for options 10-15 in Digital Out”x” Sel. Units are assumed to match the above selection (i.e., At Freq = Hz, At Torque = Amps). 386 Dig Out2 OnTime Range: 0.00 to 600.00 sec [0.01 sec] Default: 0.00 sec Access: 1 See also: 384 Path: Inputs & Output>Digital Outputs Sets the on delay time for the digital outputs.
CHAPTER 5 Troubleshooting the Drive ! ATTENTION:Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life. The LiquiFlo 1.
TP1 TP2 Control Panel Figure 5.1 – Location of DC Bus Voltage Measuring Points 5.2 Determining Drive Status Using the Inverter Status LED Inverter Status LED Control Panel Figure 5.2 – Location of the Inverter Status LED Table 5.1 – Ready LED Status Definitions Color Green Yellow See section 5.3. Red See section 5.4. 5-2 State Description Flashing Drive ready, but not running and no faults are present. Steady Drive running, no faults are present. Flashing The drive is not ready.
5.3 About Alarms Alarms indicate conditions that may affect drive operation or application performance. There are two alarm types, as described in table 5.2. Table 5.2 – Types of Alarms Type ➀ Alarm Description User-Configurable These alarms alert the operator of conditions that, if left untreated, may lead to a fault condition. The drive continues to operate during the alarm condition. The alarms are enabled or disabled using Alarm Config 1 (259).
5.3.1 Alarm Descriptions Alarm Type Table 5.3 – Alarm Descriptions Description Analog In ➀ An analog input is configured for alarm on signal loss and signal loss has occurred. Loss Bipolar Conflict ➁ Parameter 190 (Direction Mode) is set to Bipolar or Reverse Dis and one of more of the following digital input functions is configured: Fwd/Rev, Run Fwd, Run Rev, Jog Fwd, or Jog Rev. Dig In ➁ Digital input functions are in conflict. Combinations marked with a ConflictA will cause an alarm.
Alarm Type Table 5.3 – Alarm Descriptions (Continued) Description Drive OL ➀ The calculated IGBT temperature requires a reduction in Current Limit. Level 2 If Drive OL Mode (150) is disabled and the load is not reduced, an overload fault will eventually occur. Flux ➁ Result of autotune procedure (61). Amps Ref Rang IntDBRes ➀ The drive has temporarily disabled the dynamic braking regulator because the resistor temperature has exceeded a predetermined OvrHeat value.
5.4 About Faults Faults indicate conditions within the drive that require immediate attention. The drive responds to a fault by initiating a coast-to-stop sequence and turning off output power to the motor. In addition, some faults are auto-resettable, non-resettable, and/or user-configurable as described in table 5.5. Type Table 5.
The drive indicates faults in the following ways: • Inverter Status LED on the drive control panel (see section 5.2). • Drive status parameters Drive Status 1 (209) and Drive Status 2 (210). • Entries in the fault queue (see section 5.4.1). • Pop-up screen on the LCD OIM. See figure 5.3. The screen displays: • Fault number • Fault name • Time that has elapsed since fault occurred.
Refer to section 5.8.1 for information on accessing the fault queue using the LCD OIM. Refer to instruction manual D2-3488 for information on accessing the fault queue using VS Utilities software. 5.4.2 Clearing Faults A fault condition can be cleared by the following: ESC/ Step 1. Press PROG or any F-Key to acknowledge the fault and remove the fault pop-up from the LCD OIM screen. Step 2. Address the condition that caused the fault. The cause must be corrected before the fault can be cleared. Step 3.
5.4.3 Fault Descriptions and Corrective Actions Table 5.6 describes drive faults and corrective actions. It also indicates if the fault is ➀ Auto-resettable ➁ Non-resettable ➂ User-configurable Analog In Loss Type Fault No. Table 5.6 – Fault Descriptions and Corrective Actions 29 ➀ An analog input is configured 1. Check parameters. ➂ to fault on signal loss. A signal 2. Check for broken/loose loss has occurred. Description Configure with Anlg In 1, 2 Loss (324, 327).
Aux Fault 2 Gate Kill 207 Type Fault No. Table 5.6 – Fault Descriptions and Corrective Actions (Continued) Description ➀ Input is open. Check remote wiring. Inverter gsate kill contact is open. Ground Fault 13 ➀ A current path to earth ground in excess of 2A has been detected at one or more of the drive output terminals. Heatsink OvrTemp 8 Action ➀ Cooling Fan Failure Close gate kill contact. Check the motor and external wiring to the drive output terminals for a grounded condition. 1.
No. Type Table 5.6 – Fault Descriptions and Corrective Actions (Continued) OverSpeed Limit 25 ➀ Functions such as slip OverVoltage 5 Fault Description compensation or bus regulation have attempted to add an output frequency adjustment greater than that programmed in Overspeed Limit (83). ➀ DC bus voltage exceeded maximum value. ➁ The checksum read from the Remove excessive load or overhauling conditions or increase Overspeed Limit (83).
Port 1-6 Net Loss 7176 Type Fault No. Table 5.6 – Fault Descriptions and Corrective Actions (Continued) Description The network card connected to DPI port stopped communicating. The fault code indicates the offending port number (71 = port 1, etc.) Action 1. Check communication adapter board for proper connection to external network. 2. Check external wiring to adapter on port. 3. Verify external network fault.
Type Fault No. Table 5.6 – Fault Descriptions and Corrective Actions (Continued) Description Action UnderVoltage 4 ➀ DC bus voltage fell below the Monitor the incoming AC line ➂ minimum value of 407V DC at for low voltage or power 400/480V input or 204V DC at interruption. 200/240V input. Enable/disable with Fault Config 1(233). Troubleshooting the Drive ➁ The checksum read from the UserSet1 Chksum 101 UserSet2 Chksum 102 ➁ UserSet3 Chksum 103 ➁ Re-save user set.
Table 5.7 – Fault Names Cross-Referenced by Fault Number No.1 Fault 2 Function Loss 3 Power Loss No.
5.6 Common Symptoms and Corrective Actions Table 5.9 – Drive Does Not Start From Start, Run, or Jog Inputs Wired to the Terminal Block Indication(s) Flashing red Ready LED. Cause(s) Drive is faulted. Corrective Action Clear fault: • Press OIM stop key if that OIM is control source. • Cycle power. • Set Fault Clear (240) to 1. • Toggle terminal block stop or terminal block reset digital input if terminal block is kthe control source. Incorrect operation from the terminal block. Incorrect input wiring.
Table 5.9 – Drive Does Not Start From Start, Run, or Jog Inputs Wired to the Terminal Block (Continued) Indication(s) Cause(s) Corrective Action Program Digital In”x” Sel (361-366) to resolve conflicts. Remove multiple selections for the same function. Install stop button to apply a signal at stop terminal. Flashing yellow Incorrect digital input Ready LED and programming. DigIn CflctB • Mutually exclusive indication on choices have been LCD OIM. made.
Table 5.11 – Drive Does Not Respond to Changes in Speed Command Indication LCD OIM Status Line indicates “At Speed” and output is 0 Hz. Cause(s) No value is coming from the source of the command. Corrective Action 1. If the source is an analog input, check wiring and use a meter to check for presence of signal. 2. Check Commanded Freq (2) for correct source. None Incorrect reference source has been programmed. 3. Check Speed Ref Source (213) for the source of the speed reference. 4.
Table 5.13 – Motor Operation is Unstable Indication Cause(s) None Corrective Action Motor data was incorrectly 1. Correctly enter motor entered or autotune was not nameplate data. performed. 2. Perform static or rotate autotune procedure (61). Table 5.14 – Drive Will Not Reverse Motor Direction Indication Cause(s) None Corrective Action Digital input is not selected Check Digital In”x” Sel. Choose for reversing control. correct input and program for reverse. Digital input is incorrectly wired.
5.7 Replacement Parts Table 5.16 – OIM Cables Description 5.8 Part Number LCD OIM Cable for remote use RECBL-LCD LCD OIM Extender Cable (0.3 meter) RECBL-F03 LCD OIM Extender Cable (1 meter) RECBL-F10 LCD OIM Extender Cable (3 meters) RECBL-F30 LCD OIM Extender Cable (9.
FltQ# :1 F#xxxxx Fault1 Text String Accum: hours:min:sec FltQ# :2 F#xxxxx Fault2 Text String Accum: hours:min:sec Cflt Cflt Clrqu Clrqu F1 F2 F1 = Clear fault F2 = Clear fault queue Figure 5.5 – Sample Fault Queue Entry 5.8.2 Accessing the Fault Parameters The LCD OIM provides quick access to the drive’s fault parameters by grouping them in the Fault Info submenu. To access these parameters, see figure 5.6. >> Stopped Auto P0: LiquiFlo 1.
5.8.4 Determining the Product Version The LCD OIM provides hardware and firmware version information for connected devices, including the OIM, down to the component level. Device Version To access the device version information, refer to figures 5.8 and 5.9. >> Stopped Auto P0: LiquiFlo 1.5 Main Menu Diagnostics : View Fault Queue Device Version OIM Version See figure 5.9 Diagnostics Monitor Lang Highlight item Highlight Diagnostics icon Figure 5.
OIM Version The OIM Version selection provides information on the OIM you are using to access this data. See figures 5.10 and 5.11. >> Stopped Auto P0: LiquiFlo 1.5 Main Menu Diagnostics : OIM Version Fault Info Status Info See figure 5.11 Diagnostics Lang Monitor Highlight item Highlight Diagnostics icon Figure 5.10 – Accessing the OIM Version Information Diag: Prodct Ver FW Ver: x.
Device Items The Device Items selection provides access to a list of diagnostic parameters. These parameters should be adjusted by qualified personnel only. See figure 5.12. ! >> ATTENTION:The parameters in the Device Items menu must be set by a qualified person who understands the significance of setting them accurately. Failure to observe this precaution could result in bodily injury. Stopped Auto P0: LiquiFlo 1.
5-24 LiquiFlo 1.5 AC Drive, Software Reference Version 1.
APPENDIX A Parameters Cross-Referenced by Name The following table lists the complete set of LiquiFlo parameters in alphabetical order. Parameter Name No. Path (File>Group) Page No.
Parameter Name Analog In3 Value No. 18 Path (File>Group) Page No.
Parameter Name No. Path (File>Group) Page No.
Parameter Name No.
Parameter Name No. Path (File>Group) Page No.
Parameter Name No. Path (File>Group) Page No.
Parameter Name No. Path (File>Group) Page No.
Parameter Name No. Path (File>Group) Page No.
Parameter Name No. Path (File>Group) Page No.
Parameter Name No. Path (File>Group) Page No.
APPENDIX B Parameters in the Basic Access Level The following parameters are accessible when the Basic access level (0) is selected. No. Parameter Name Path (File>Group) Page No.
No. B-2 Parameter Name Path (File>Group) Page No.
No. Parameter Name Path (File>Group) Page No.
B-4 LiquiFlo 1.5 AC Drive, Software Reference Version 1.
APPENDIX C Record of User Settings: Basic Access Level No.
No.
No.
C-4 LiquiFlo 1.5 AC Drive, Software Reference Version 1.
APPENDIX D Record of User Settings: Advanced Access Level No.
No.
No.
No.
No.
No.
No.
D-8 LiquiFlo 1.5 AC Drive, Software Reference Version 1.
INDEX A C Accel Time 1 (140), 4-33 Accel Time 2 (141), 4-33 Access levels, parameter, 3-4 Alarm 1 @ Fault (229), 4-55 Alarm 2 @ Fault (230), 4-55 Alarm Config 1 (259), 4-59 Alarms about, 5-4 descriptions, 5-5 names cross-referenced to numbers, 5-6 Analog In 1 Hi (322), 4-69 Analog In 1 Lo (323), 4-70 Analog In 1 Loss (324), 4-70 Analog In 2 Hi (325), 4-71 Analog In 2 Lo (326), 4-71 Analog In 2 Loss (327), 4-71 Analog In1 Value (16), 4-4 Analog In2 Value (17), 4-4 Analog In3 Value, 4-4 Analog Out Config (3
Dig Out2 OffTime (387), 4-83 Dig Out2 OnTime (386), 4-83 Digital In1 Sel (361), 4-75 Digital In2 Sel (362), 4-75 Digital In3 Sel (363), 4-75 Digital In4 Sel (364), 4-75 Digital In5 Sel (365), 4-75 Digital In6 Sel (366), 4-75 Digital Out1 Sel (380), 4-81 Digital Out2 Sel (384), 4-82 Direction Mode (190), 4-42 Display timeout period, setting, 2-12 DPI Baud Rate (270), 4-60 Drive Alarm 1 (211), 4-49 Drive Alarm 2 (212), 4-49 Drive Checksum (203), 4-46 Drive Logic Rslt (271), 4-60 Drive OL Count (219), 4-52 Dri
Motor NP FLA (42), 4-9 Motor NP Hertz (43), 4-10 Motor NP Power (45), 4-10 Motor NP RPM (44), 4-10 Motor NP Volts (41), 4-9 Motor OL Count (220), 4-53 Motor OL Factor (48), 4-11 Motor OL Hertz (47), 4-11 Motor Type (40), 4-9 Mtr NP Pwr Units (46), 4-10 N Network status LEDs, 5-3 O OIM reference, displaying and changing, 2-9 OIM, LCD cables, 2-1 connections, 2-1 display description, 2-3 display timeout period, setting, 2-12 drive status parameters, accessing, 5-20 fast power up, 2-6 fault parameters, acces
Process display screen, LCD OIM, 2-8 Product version, how to determine, 5-21 Program protection, 3-6 Programming basics, 3-1 Q Status 2 @ Fault (228), 4-54 Stop Mode A (155), 4-35 Stop Mode B (156), 4-35 Stop Owner (288), 4-64 Stopping the drive using the LCD OIM, 2-14 SV Boost Filter (59), 4-15 Quickstart parameters, 1-3 T R TB Man Ref Hi (97), 4-23 TB Man Ref Lo (98), 4-23 TB Man Ref Sel (96), 4-22 Test point codes and functions, 5-14 Testpoint 1 Data (235), 4-56 Testpoint 1 Sel (234), 4-56 Testpoin
U.S. Drives Technical Support Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: support@drives.ra.rockwell.com, Online: www.ab.com/support/abdrives Publication D2-3495-November 2001 Copyright © 2001 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.