User Manual Instruction Manual

Wiring Requirements for the Drive
4-13
Note: For 325 VDC input drives, contact the factory.
Table 4.7 – DC Common Bus Input Fuse Selection Values
Model
Number
6V41
Frame
Nominal Power Ratings 650 VDC
110% OL Duty 150% OL Duty
Fuse Rating Bussmann Style FusekW HP kW HP
-1P1xx 0 .37 0.5 .25 .33 6
Bussmann_JKS-6
-2P1xx 0 .75 1 .55 .75 6
Bussmann_JKS-6
-3P4xx 0 1.5 2 1.1 1.5 6
Bussmann_JKS-6
-5P0xx 0 2.2 3 1.5 2 10
Bussmann_JKS-10
-8P0xx 0 4 5 2.2 3 15
Bussmann_JKS-15
-011xx 0 5.5 7.5 4 5 20
Bussmann_JKS-20
-014xx 1 7.5 10 5.5 7.5 30
Bussmann_JKS-30
-022xx 1 11 15 7.5 10 45
Bussmann_JKS-45
-027xx215201115 60
Bussmann_JKS-60
-034xx 2 18.5 25 15 20 70
Bussmann_JKS-70
-040xx 3 22 30 18.5 25 80
Bussmann_JKS-80
-052xx 3 30 40 22 30 100
Bussmann_JKS-100
-065xx 3 37 50 30 40 150
Bussmann_JKS-150
-077xx 4 45 60 - - 150
Bussmann_JKS-150
- - 37 50 150
Bussmann_JKS-150
Model
Number
6VJ1/6VR1
Frame
Nominal Power Ratings 650 VDC
110% OL Duty 150% OL Duty
Fuse Rating Bussmann Style FusekW HP kW HP
-096xx 5 55 75 - - 150
Bussmann_JKS-150
- - 45 60 200
Bussmann_JKS-200
-125xx 5 55 100 - - 200
Bussmann_JKS-200
- - 45 75 250
Bussmann_JKS-250
-156xx 6 93 125 - - 250
Bussmann_JKS-250
- - 75 100 300
Bussmann_JKS-300
-180xx 6 110 150 - - 300
Bussmann_JKS-300
- - 100 125 400
Bussmann_JKS-400
-248xx 6 132 200 - - 400
Bussmann_JKS-400
- - 110 150 400
Bussmann_JKS_400