User Manual Instruction Manual
4-12
GV6000 AC Drive User Manual
Table 4.6 – AC Line Input Fuse Selection Values (600 VAC)
Model
Number
6V51
Frame
Nominal Power Ratings
Dual Element
Time Delay Fuse
Non-time
Delay Fuse
Circuit
Breaker
110% OL Duty 150% OL Duty 600 VAC 600 VAC 600 VAC
kW HP kW HP Min Max Min Max A
-1P7xx0.751.330.52 4 26 15
-2P7xx 0 1.5 2 .75 1 3 6 3 10 15
-3P9xx 0 2.2 3 1.5 2 6 9 6 15 15
-6P1xx 0 4 5 2.2 3 9 12 9 20 20
-9P0xx 0 5.5 7.5 4 5 10 20 10 35 30
-011xx 1 7.5 10 5.5 7.5 15 25 15 40 40
-017xx 1 11 15 7.5 10 20 40 20 60 50
-022xx 2 15 20 11 15 30 50 30 80 80
-027xx220 25 15 20 35 60 35100 100
-032xx325 30 20 25 40 70 40125 125
-041xx330 40 25 30 50 90 50150 150
-052xx 3 37 50 30 40 60 110 60 200 200
-062xx 4 45 60 37 50 80 125 80 225 225
-077xx 5 55 75 - - 90 150 90 300 300
- - 45 60 90 125 90 250 250
-099xx 5 75 100 - - 125 200 125 375 375
- - 55 75 100 175 100 300 300
-125xx 6 90 125 - - 150 250 150 375 375
- - 75 100 125 200 125 375 375
-144xx 6 110 150 - - 175 300 175 400 400
- - 90 125 150 275 150 375 375