User Manual Instruction Manual
Wiring Requirements for the Drive
4-11
Table 4.5 – AC Line Input Fuse Selection Values (480 VAC)
Model
Number
6V41
Frame
Nominal Power
Ratings
Dual Element Time
Delay Fuse
Non-time Delay
Fuse Circuit Breaker
110% OL
Duty
150% OL
Duty 480 VAC 400 VAC 480 VAC 400 VAC
480
VAC
400
VAC
kW HP kW HP Min Max Min Max Min Max Min Max A A
-1P1xx0.370.5.25.3333333636 15 15
-2P1xx0.751.55.7536363838 15 15
-3P4xx 0 1.5 2 1.1 1.5 4 8 6 7 4 12 6 12 15 15
-5P0xx 0 2.2 3 1.5 2 6 10 6 10 6 20 6 20 20 20
-8P0xx04 52.2310151517.510301530 30 30
-011xx05.57.5 4 5 1520152515401545 40 45
-014xx 1 7.5 10 5.5 7.5 17.5 30 20 30 17.5 50 20 60 50 60
-022xx 1 11 15 7.5 10 25 50 30 45 25 80 30 80 80 80
-027xx 2 15 20 11 15 35 60 35 60 35 100 35 120 100 120
-034xx 2 18.5 25 15 20 40 70 45 80 40 125 45 125 125 125
-040xx 3 22 30 18.5 25 50 90 60 90 50 150 60 150 150 150
-052xx 3 30 40 22 30 60 110 70 125 60 200 70 200 200 200
-065xx 3 37 50 30 40 80 125 90 150 80 250 90 250 250 250
-077xx 4 45 60 - - 100 170 110 200 100 300 110 300 300 300
- - 37 50 80 125 90 175 80 250 90 275 250 300
-096xx 5 55 75 - - 125 200 150 275 125 350 150 500 350 375
- - 45 60 100 170 125 200 100 300 125 375 300 375
-125xx 5 55 100 - - 150 250 200 300 150 500 200 400 375 400
- - 45 75 125 200 150 225 125 350 150 300 350 300
-156xx 6 93 125 - - 200 350 250 375 200 600 250 600 450 500
- - 75 100 175 250 200 300 175 500 200 550 375 400
-180xx 6 110 150 - - 225 400 250 450 225 600 250 600 500 600
- - 100 125 200 350 250 375 200 600 250 600 450 500
-248xx 6 132 200 - - 300 550 350 550 300 700 350 750 700 750
- - 110 150 225 400 250 450 225 600 250 600 500 600