User Manual Instruction Manual

4-10
GV6000 AC Drive User Manual
IEC and UL - devices are acceptable for IEC and UL installations.
Table 4.4 – AC Line Input Fuse Selection Values (240 VAC)
Model
Number
6V21
Frame
Nominal Power
Ratings
Dual Element Time
Delay Fuse
Non-time Delay
Fuse Circuit Breaker
110% OL
Duty
150% OL
Duty 240 VAC 200 VAC 240 VAC 200 VAC
240
VAC
200
VAC
kW HP kW HP Min Max Min Max Min Max Min Max A A
-2P2xx 0 .37 0.5 .25 .33 3 6 3 6 3 10 3 10 15 15
-4P2xx 0 .75 1 .55 .75 5 8 6 10 5 15 6 17.5 15 15
-6P8xx11.5 2 1.11.510151015102510 30 25 30
-9P6xx12.2 3 1.5 2 12 20 1220123512 40 35 40
-015xx1 4 5 2.2 3 20 30 2035206020 70 60 70
-022xx 1 5.5 7.5 4 5 25 50 30 50 25 80 30 100 80 100
-028xx 2 7.5 10 5.5 7.5 35 60 40 70 35 100 40 125 100 125
-042xx 3 11 15 7.5 10 50 90 60 100 50 150 60 175 150 175
-052xx 3 15 20 11 15 60 100 80 125 60 200 80 200 200 200
-070xx 4 18.5 25 15 20 90 150 90 175 90 275 90 300 275 300
-080xx 4 22 30 18.5 25 100 180 110 200 100 300 110 350 300 350
-104xx 5 30 40 - - 125 225 150 250 125 400 150 475 300 350
- - 22 30 100 175 125 200 100 300 125 350 300 300
-130xx 5 37 50 - - 175 275 175 275 175 500 175 500 375 375
- - 30 40 125 225 125 225 125 400 125 400 300 300
-154xx 6 45 60 - - 200 300 225 350 200 600 225 500 450 500
- - 37 50 175 275 200 300 175 500 200 500 375 450
-192xx 6 55 75 - - 225 400 300 450 225 600 300 600 575 600
- - 45 60 200 300 225 350 200 600 225 500 450 500
-260xx 6 75 100 - - 250 450 250 450 250 600 250 600 600 600
- - 55 75 350 550 350 550 350 750 350 750 750 750