4.4 Recommended Motor Lead Lengths
Important: To reduce nuisance tripping and possible equipment damage, motor lead
length should not exceed (91 meters) 300 feet for any non-Reliance
Electric motor or any non-inverter duty motor.
The length of cable between the drive and motor may be limited for various application
reasons. The primary areas of concern are:
• Insulation damage due to Reflected wave
• Cable charging
When total lead length exceeds 300 feet, nuisance trips caused by capacitive current
flow to ground can occur. Note that these capacitively-coupled currents should be
taken into consideration when working in areas where drives are running. If the motor
lead length must exceed these limits, the addition of output reactors or other steps
must be taken to avoid problems.
Your application may be restricted to a shorter lead length due to:
• The type of wire (shielded or unshielded)
• The placement of wire (for example, in conduit or a cable tray)
• The type of line reactor
• The type of motor (voltage class, 1000 V, 1200 V, or 1600 V)
• Drive carrier frequency
Figure 4.1 illustrates how to calculate motor lead lengths. The examples shown
assume a maximum lead length of 300 feet.
Figure 4.1 – How to Calculate Motor Lead Lengths
GV6000
Drive
Motor
150
′
150
′
50
′
250
′
200’
50
′
50
′
300
′
Motor
Motor
Motor
Motor Motor
Motor
GV6000
Drive
GV6000
Drive
GV6000
Drive