GV6000 AC Drive User Manual
“Continue” – Allow the drive to power the motor down to half bus voltage.
Sets the reaction to a loss of input power. Power loss is recognized when:
DC bus voltage is 73% of DC Bus Memory and Power Loss Mode is set to Coast.
DC bus voltage is 82% of DC Bus Memory and Power Loss Mode is set to Decel.
13.34.4 Coast
This is the default mode of operation.
The drive determines a power loss has occurred if the bus voltage drops below
Vtrigger. If the drive is running the inverter output is disabled and the motor coasts.
The power loss alarm in Drive Alarm 1(211) is set and the power loss timer starts.
The Alarm bit in Drive Status 1 (209) is set if the Power Loss bit in Alarm Config 1(211)
is set.
The drive faults with a F003 – Power Loss Fault if the power loss timer exceeds Power
Loss Time (185) and the Power Loss bit in Fault Config 1 (238) is set.
The drive faults with a F004 – UnderVoltage fault if the bus voltage falls below Vmin
and the UnderVoltage bit in Fault Config 1 (238) is set.
The pre-charge relay opens if the bus voltage drops below Vopen and closes if the bus
voltage rises above Vclose
If the bus voltage rises above Vrecover for 20mS, the drive determines the power loss
is over. The power loss alarm is cleared.
184 Power Loss Mode
Range: 0 = Coast
1 = Decel
2 = Continue
3 = Coast input
4 = Decel input
Default: 0 = Coast
Access: 1 Path: Dynamic Control>Power Loss
See also: 13, 184