User Manual Instruction Manual

Application Notes
13-59
Setup
Analog Out1 Sel (342) = 14 “Commanded Torque”
Analog Out1 Hi (343) = 10.000 Volts
Analog Out1 Lo (344) = 0.000 Volts
Anlg Out1 Scale (354) = 100.0
If Analog Out1 Lo (344) = –10.000 Volts the output will be –10.0 to +10.0V DC for
–100% to +100% Commanded Torque.
If Anlg Out1 Scale (354) = 0.0, the default scaling listed in Analog Out1 Sel (342) will
be used. This would be 0-1.25V DC for 0-100% Torque or 0-800% for 0-10V DC.
13.20.6.2 Scale Block Analog Output
Selects scaled analog output relative to the Scale Block value. Values not in the
Analog OutX Sel parameter list can be used to drive the analog outputs. When using
the Scale Block select, the Scale block Out Hi and Out Lo parameters are not used.
Example
Analog Output 2 set for 0-10V DC for Heat Sink Temp 0-100 Degrees C. using Scale
Block 1.
Setup
Link Scale1 In Value (476) to Testpoint 1 Data, (235)
Testpoint 1 Sel (234) = 2 “Heat Sink Temp”
Analog Out2 Sel (345) = 20 “Scale Block 1”
Analog Out2 Hi (346) = 10.000 Volts
Analog Out2 Lo (347) = 0.000 Volts
Scale1 In Hi (477) = 100
Scale1 In Lo (478) = 0
477
In Lo
In Hi
In Hi
Out Lo
Out
Out Hi
235
Testpoint 1 Data
476
478
479
481
480
Scale 1
Link