User Manual Instruction Manual

13-48
GV6000 AC Drive User Manual
13.19.3.4 Configuration #4:
Anlg In Config (320), bit 0 = “0” (Voltage)
Speed Ref A Sel (90) = “Analog In 1”
Speed Ref A Hi (91) = 0 Hz
Speed Ref A Lo (92) = 60 Hz
Analog In 1 Hi (322) = 10V
Analog In 1 Lo (323) = 0V
This configuration is used to invert the operation of the input signal. Here, maximum
input (10 Volts) represents 0 Hz and minimum input (0 Volts) represents 60 Hz.
Analog Scaling
4
8
12
16
20
601218
Output Hertz
Input mA
24 30 36 42 48 54 60
Speed Ref A Sel (90) = “Analog In 1”
Analog In 1Hi (322)
10 V
Speed Ref A Hi (91)
0 Hz
Analog In 1Lo (323)
0 V
Speed Ref A Lo (92)
60 Hz
2
4
6
8
10
601218
Output Hertz
Input Volts