User Manual Instruction Manual

13-40
GV6000 AC Drive User Manual
13.18 Voltage Tolerance
Drive Full Power Range = Nominal Motor Voltage to Drive Rated Voltage + 10%.
Rated power is available across the entire Drive Full Power Range.
Drive Operating Range = Lowest(*) Nominal Voltage -10% to Drive Rated Voltage
+10%. Drive Output is linearly derated when Actual Line Voltage is less than the
Nominal Motor Voltage.
13.18.1 Example
Calculate the maximum power of a 5 HP, 460V motor connected to a 480V rated drive
supplied with 342V Actual Line Voltage input.
Actual Line Voltage / Nominal Motor Voltage = 74.3%
74.3% × 5 HP = 3.7 HP
74.3% × 60 Hz = 44.6 HzAt 342V
Drive Rating
Nominal Line
Voltage
Nominal
Motor
Voltage
Drive Full
Power Range
Drive
Operating
Range
200-240 200 200* 200-264 180-264
208 208 208-264
240 230 230-264
380-400 380 380* 380-528 342-528
400 400 400-528
480 460 460-528
500-600
(
Frames 0-4
Only)
600 575* 575-660 432-660
500-690
(
Frames 5-6
Only)
600 575* 575-660 475-759
HP @ Motor (Drive Output)
Actual Line Voltage (Drive Input)
Full Power Range
Drive Operating Range
Nominal Motor Voltage -10%
Nominal Motor Voltage
Derated Power Range
Drive Rated Voltage
Drive Rated Voltage +10%