GV6000 AC Drive User Manual
• Grounding as described in section 3.4 of this manual.
• Output power, control (I/O) and signal wiring must be braided, shielded cable with a
coverage of 75% or better, metal conduit or equivalent attenuation.
• All shielded cables should terminate with the proper shielded connector.
Table 2.6 – GV6000 AC Drive EN1800-3 EMC Compatibility
Frame
Drive Description Second Environment
1
1.Motor cable limited to 30 m (98 ft) for installations in the second (industrial) environment without
additional external line filters.
First Environment
Restricted Distribution
0-6 Drive with any options
• Restrict motor cable to
30 m (98 ft)
• Restrict motor cable to
150 m (492 ft)
• Install External filter