User Manual Instruction Manual

13-36
GV6000 AC Drive User Manual
13.16 Start At Powerup
A powerup delay time of up to 30 seconds can be programmed through Powerup
Delay (167). After the time expires, the drive will start if all of the start permissive
conditions are met. Before that time, restart is not possible.
13.17 Stop Mode
The GV6000 offers several methods for stopping a load. The method/mode is defined
by Stop/Brk Mode A/B (155 and 156). These modes include:
Coast
Ramp
Ramp to Hold
DC Brake
Fast Brake
Additionally, Flux Braking (166) can be selected separately to provide additional
braking during a “Stop” command or when reducing the speed command. For “Stop”
commands, this will provide additional braking power during “Ramp” or “Ramp to
Hold” selections only. If “Fast Brake” or “DC Brake” is used, “Flux Braking” will only be
active during speed changes (if enabled).
Powerup Delay (167)
Time Expired?
Start At PowerUp
Ye s
Powerup Terminated!
Normal Mode
No
No
No
Powerup Start
Is the terminal block Run,
Run Forward or Run Reverse
Input Closed?
Ye s
Ye s
All Start Permissives Met?
1. No fault conditions present.
2. No Type 2 alarm conditions present.
3. The terminal block programmed
enable input is closed.
4. The Stop input (from all sources) is
received.