User Manual Instruction Manual

Application Notes
13-35
Figure 13.16 – Sleep Wake Mode
Is Sleep-Wake
Working?
Have these conditions been met?
Is Required Input Closed?
(Stop, Enable, Run)
Did a Drive
Fault Occur?
Which Required Input
was Chosen?
Meet all Conditions!
Close Input
Reset Fault
Ye s
Ye s
Stop or Enable
Run, Run Forward
or Run Reverse
Ye s
Ye s
Drive Running?
No
DirectInvert
No
No
No
No
No
No
Issue a Start Command
(OIM, Network or TB)
Open & Close Input
Consult Factory
No
Consult Factory
Which Mode is Selected?
"Invert" or "Direct"
1. Sleep-Wake Ref (179) must be set to the analog input that will control
"Start/Stop" functions.
2. Sleep-Wake Mode (178) must = "1, Direct" (Enable) or "2, Invert
(Enable)."
3. Sleep Level (182) must be less than Wake Level (180) in Direct mode
(or greater than Wake Level (180) in "Invert" mode).
4. Speed Ref x Sel must be set to a speed reference source that will
control the drive. If Sleep-Wake Ref (179) = Speed Ref x Sel, the same
analog signal will control start/stop and speed reference.
5. At least one of the following must be programmed for [Digital Inx Sel]:
Is Analog Signal
Greater
than or equal to Wake Level (180)?
and for time period greater than or
equal to Wake Time (181)
Ye s Ye s
Is Analog Signal
Less
than or equal to Wake Level (180)?
and for time period greater than or
equal to Wake Time (181)
Increase Analog Input Signal
and wait for a time period
greater than or equal to
Wake Time (181).
Decrease Analog Input
Signal and wait for a time
period greater than or equal
to Wake Time (181).
Was a Stop Issued?
or
Power Cycled?