13.14 Skip Frequency
Some machinery may have a resonant operating frequency that must be avoided to
minimize the risk of equipment damage. To assure that the motor cannot continuously
operate at one or more of the points, skip frequencies are used. Parameters 084-086,
(Skip Frequency 1-3) are available to set the frequencies to be avoided.
The value programmed into the skip frequency parameters sets the center point for an
entire βskip bandβ of frequencies. The width of the band (range of frequency around
the center point) is determined by parameter Skip Freq Band (87). The range is split,
half above and half below the skip frequency parameter.
If the commanded frequency of the drive is greater than or equal to the skip (center)
frequency and less than or equal to the high value of the band (skip plus 1/2 band),
the drive will set the output frequency to the high value of the band. See (A) in Figure
13-15.
If the commanded frequency is less than the skip (center) frequency and greater than
or equal to the low value of the band (skip minus 1/2 band), the drive will set the output
frequency to the low value of the band. See (B) in Figure 13-15.
Figure 13.15 β Skip Frequency
Frequency
Time
(A)
(A)
(B)
(B)
Skip Frequency
Command
Frequency
Drive Output
Frequency
Skip + 1/2 Band
Skip β 1/2 Band
35 Hz
30 Hz
25 Hz