User Manual Instruction Manual

Troubleshooting the Drive
12-19
12.7 Common Symptoms and Corrective Actions
!
ATTENTION:Remove power from the drive. DC bus capacitors retain
hazardous voltages after input power has been removed. After
disconnecting input power, wait five minutes for the DC bus capacitors
to discharge and then check the voltage with a voltmeter to ensure the
DC bus capacitors are discharged before touching any internal
components. Failure to observe this precaution could result in severe
bodily injury or loss of life.
Table 12.10 – Drive Does Not Start From Start, Run, or Jog Inputs Wired to the Terminal Block
Indication(s) Cause(s) Corrective Action
Flashing red
Ready LED.
Drive is faulted. Clear fault:
Press stop.
Cycle power.
Set Fault Clear (240) to 1.
“Clear Faults” on the OIM Diagnostic
Menu.
Incorrect
operation from
the terminal
block.
Incorrect input wiring.
2-wire control requires
Run, Run Forward, or
Run Reverse input(s).
3-wire control requires
Start and Stop inputs
Jumper from terminal
25 to 26 is required.
Wire inputs correctly and/or install
jumper.
Incorrect digital input
programming.
Mutually exclusive
choices have been
made.
2-wire and 3-wire
programming may be
conflicting.
Exclusive functions
(i.e, direction control)
may have multiple
inputs configured.
Stop if factory default
and is not wired or is
open.
Program Digital In”x” Sel (361-366) for
correct inputs.
Start or Run programming may be
missing.