User Manual Instruction Manual
12-18
GV000 AC Drive User Manual
12.6 Testpoint Parameter
Select testpoint with Testpoint X Sel (234, 236). Values can be viewed with Testpoint X
Data (235, 237).
33 Auto Rstrt Tries 79 Excessive Load 131 Hardware Fault
36 SW OverCurrent 80 AutoTune Aborted
38 Phase U to Grnd 81- 85 Port 1-5 DPI Loss
1
Fault numbers not listed are reserved for future use.
Table 12.8 – Fault Names Cross-Referenced by Fault Number
No.
1
Fault No.
1
Fault No
1
Fault
Table 12.9 – Test Point Codes and Functions
Number
1
1
Enter in Testpoint x Sel.
Description Default
01 DPI Error Status 0
02 Heatsink Temp 0
03 Active Cur Limit 0
04 Active PWM Freq 4
05
Lifetime MegaWatt Hours
2
2
Use the equation below to calculate total Lifetime MegaWatt Hours.
0
06 Life Run Time 0
07 Life Pwr Up Time 0
08 Life Pwr Cycles 0
09
Life MW-HR Fract
2
0
10
MW-HR Fract Unit
2
0
11 MCN Life Time
0
12 Raw Analog ln 1
0
13 Raw Analog ln 2
0
16 CS Msg Rx Cnt
0
17 CS Msg Tx Cnt
0
18 CS Timeout Cnt
0
19 CS Msg Bad Cnt
0
22 PC Msg Rx Cnt
0
23 PC Msg Tx Cnt
0
24-29 PC1-6 Timeout Cnt
0
30 CAN BusOff Cnt
0
31 No. of Analog Inputs
0
32 Raw Temperature
0
33 MTO Norm Mtr Amp
0
34 DTO-Cmd Frequency
0
35 DTP-Cmd Cur Lim
0
36 DTO-Cmd DC Hold
0
37 Control Bd Temp 0.0
Value of Code 9
Value of Code 10
------------------------------------------
0.1×
Value of Code 5+ Total Lifetime Megawatt Hours=