Motor
Ty pe C f l c t
21
Motor Type (90) has been set to Sync PM or Sync Reluc, and one or
more of the following exist:
Torque Perf Mode = “Sensrls Vect,” “SV Economizer” or “Fan/Pmp
V/Hz.
Flux Up Time is greater than 0.0 secs.
Speed Mode is set to “Slip Comp.
Autotune = “Static Tune” or “Rotate Tune.
NP Hz
Conflict
22
Fan/pump mode is selected in Torq Perf Mode (53), and the ratio of
Motor NP Hertz (43) to Maximum Freq (55) is greater than 26.
Power
Loss
3
Drive has sensed a power line loss.
Precharge
Actv
1
Drive is in the initial DC bus precharge state.
Prof Step
Cflct
50
An error is detected in trend step(s).
Set if Sleep mode is enabled
Set if:
any profile step uses “Encoder Incr” and/or “Enc Absolute” and
Motor Cntl Sel (53) is not set to “FVC Vector” and Feedback
Select (80) is not set to “Encoder” or “Simulator” and
Speed/Torque Mod (88) = “7” (Pos/Spd Prof).
a Step Type is configured for “Dig Input” and the Step Value is
greater than 6, less than -6, or zero or the digital input selected
with Digital lnx Sel is not set to “57” (Prof Input).
Cleared if none of the above occur.
PTC
Conflict
31
PTC is enabled for Analog ln 1, which is configured as a 0-20 mA
current source in Anlg ln Config (320).
Sleep
Config
29
Sleep/Wake configuration error. With Sleep-Wake Mode (178) =
Direct, possible causes include: drive is stopped and Wake Level <
Sleep Level. “Stop=CF”, “Run,” “Run Forward” and “Run Reverse” is
not configured in Digital lnx Sel.
Speed
Ref Cflct
27
Speed Ref x Sel or PI Reference Sel is set to “Reserved.
Start At
Powerup
4
Start At Powerup (168) is enabled. Drive may start at any time
within 10 seconds of drive powerup.
Table 12.4 – Alarm Descriptions (Continued)
Alarm
No.
Type
Description