User Manual Instruction Manual
11-140
GV6000 AC Drive User Manual
TBD
Integral gain for the Frequency Regulator.
Proportional gain for the Frequency Regulator.
Angle used to compensate for long cables attached to inverter and motor. Identified
during autotune for Encoderless FVC.
538 Rec Delay Time
Range: 1 to 30000 [1]
Default: 1000
Access: 2 Path: Utility>Diag-Motor Cntl
See also:
539 Ki Freq Reg
Range: 0 to 32767 [1]
Default: 450
Access: 2 Path: Utility>Diag-Vector Cnt
See also:
540 Kp Freq Reg
Range: 0 to 32767 [1]
Default: 2000
Access: 2 Path: Utility>Diag-Vector Cnt
See also:
541 Encdlss Ang Comp
Range: -1023 to 1023 [1]
Default: 0
Access: 2 Path: Utility>Diag-Vector Cnt
See also: