GV6000 AC Drive User Manual
Load Spd Lim = Enables drive to perform load calculation at base speed. Drive will
then limit operation above base speed depending on load.
NoEnclsBkSlp = A “1” disables the partial Brake Slip routine from the drive when
encoderless is selected.
Allows control of specific torque proving functions through a communication device.
Defines the allowable difference between the commanded frequency and encoder
feedback value. A fault will occur when the difference exceeds this value for a period
of time.
Sets the amount of time before a fault is issued when Spd Dev Band (602) is outside
its threshold.
601 TorqProve Setup
Range: See figure 11.39
Default: See figure 11.39
Access: 2 Path: Applications>Torque Proving
See also:
Figure 11.39 – TorqProve Setup
0000
xxxxxxxxxxxx
10 01234567891112131415
1
=Enabled
0
=Disabled
x =Reserved
Bit #
Factory Default Bit Values
Fast Stop
Micro Pos
Decel Limit
End Stop
602 Spd Dev Band
Range: 0.1 to 15.0 Hz or 3.0 to 450.0 RPM [0.1 Hz or 0.1 RPM]
Default: 2.0 Hz or 60.0 RPM
Access: 2 Path: Applications>Torque Proving
See also: 603
603 Spd Band Integrat
Range: 1 to 200 mSec [1 mSec]
Default: 60 mSec
Access: 2 Path: Applications>Torque Proving
See also: 602