User Manual Instruction Manual

11-108
GV6000 AC Drive User Manual
Refer to the formula below:
PI
Out
= KD (Sec) x (d
PI Error
(%))/(d
t
(Sec))
Scales the upper value of PI Reference Sel (126) of the source.
Scales the lower value of PI Reference Sel (126) of the source.
Scales the upper value of PI Feedback Sel (128) of the source.
Scales the lower value of PI Feedback Sel (128) of the source.
459 PI Deriv Time
Range: 0.00 to 100.00 secs [0.01 sec]
Default: 0.0 sec
Access: 2 Path: Speed Command>PI Process
See also:
FV
460 PI Reference Hi
Range: -/+ 100.00% [0.1%]
Default: 100.0%
Access: 2 Path: Speed Command>PI Process
See also:
461 PI Reference Lo
Range: -/+ 100.00% [0.1%]
Default: -100.0%
Access: 2 Path: Speed Command>PI Process
See also:
462 PI Feedback Hi
Range: -/+ 100.00% [0.1%]
Default: 100.0%
Access: 2 Path: Speed Command>PI Process
See also:
463 PI Feedback Lo
Range: -/+ 100.00% [0.1%]
Default: 0.0%
Access: 2 Path: Speed Command>PI Process
See also: