User Manual Instruction Manual
Parameter Descriptions
11-105
Defines the torque limit for the negative torque reference value. The reference will not
be allowed to exceed this value.
Provides an internal fixed value for Torque Setpoint when Torque Ref Sel is set to
Torque Setpt2.
Displays a summary status of any condition that may be limiting either the current or
the torque reference.
437 Neg Torque Limit
Range: -800.0% to 0.0 [0.1%]
Default: -200.0%
Access: 1 Path: Motor Control>Torq Attributes
See also: 53
FV
438 Torque Setpoint2
Range: -/+ 800.0% [0.1%]
Default: 0.0%
Access: 1 Path: Motor Control>Torq Attributes
See also:
FV
440 Control Status
Range: See figure 11.37
Default: Read Only
Access: 1 Path: Motor Control>Torq Attributes
See also: 53
FV
Figure 11.37 – Control Status
0000000000000000
10 01234567891112131415
1
=Condition True
0
=Condition False
x =Reserved
Bit #
NegTrqCurLim
PosTrqCurLim
NegFlxCurLim
PosFlxCurLim
NegTrqLim
it
PosTrqLim
it
NegPw
rTrqLim
PosPw
rTrqLim
M
in Slip Lim
M
ax Slip Lim
M
inTrqCurLim
VelTrqRef
TorqRef
FldW
eakSts
O
bserve Sts
VltLim
Leakag
00000
xxxxxxxxxxx
26 161718192021222324252728293031
1
=Condition True
0
=Condition False
x =Reserved
Bit #
VltLimStator
DrvVoltLim
FluxBrake
Economize
RevPhaseMot