User Manual Instruction Manual

11-94
GV6000 AC Drive User Manual
Sets the digital output value from a communication device.
Example: Set Data ln B1 (302) to 379. The first three bits of this value will determine
the setting of Digital Outx Sel (380, 384, 388), which should be set to 30 = Param Cntl.
379 Dig Out Setpt
Range: See figure 11.34
Default: See figure 11.34
Access: 2 Path: Inputs & Outputs>Digital Outputs
See also: 380
Figure 11.34 – Dig Out Setpt
00
x
0
xxxxxxxxxxxx
10 01234567891112131415
1
=Output Energized
0
=Output De-energized
x =Reserved
Bit #
Digital Out1
Digital Out2
Digital Out3