User Manual Instruction Manual

2-4
GV6000 AC Drive User Manual
Table 2.3 – 600 VAC Power Ratings
Model
Number
6V51
Frame
Output Amps Nominal Power Ratings External
Watts
Loss @
4 kHz
@600
VAC
Internal
Watts
Loss @
4 kHz
@600
VAC
Watts
Loss @
4 kHz
@600
VAC
600 VAC Input
110% OL
Duty
150% OL
Duty
Input
KVA
@600
VAC
Input
Amps
@600
VACCont 1 Min 3 Sec kW HP kW HP
-1P7xx 0 1.7 2 2.6 .75 1 .33 0.5 1.4 1.3 14 40 54
-2P7xx 0 2.7 3.6 4.8 1.5 2 .75 1 2.1 2.1 25 40 65
-3P9xx 0 3.9 4.3 5.9 2.2 3 1.5 2 3.1 3 41 42 83
-6P1xx 0 6.1 6.7 9.2 4 5 2.2 3 5.5 5.3 59 83 142
-9P0xx 0 9 9.9 13.5 5.5 7.5 4 5 8.1 7.8 83 75 157
-011xx 1 11 13.5 18 7.5 10 5.5 7.5 10.2 9.9 109 77 186
-017xx 1 17 18.7 25.5 11 15 7.5 10 16 15.4 177 93 270
-022xx 2 22 25.5 34 15 20 11 15 21 20.2 260 83 343
-027xx 2 27 33 44 20 25 15 20 25.7 24.8 291 95 385
-032xx 3 32 40.5 54 25 30 20 25 30.5 29.4 324 95 419
-041xx 3 41 48 64 30 40 25 30 39.1 37.6 459 109 569
-052xx 3 52 61.5 82 37 50 30 40 49.6 47.7 569 141 710
-062xx 4 62 78 104 45 60 37 50 60.5 58.2 630 195 825
-077xx 5 77 85 116 55 75 - - 75.1 72.3 1053 308 1361
63 94 126 - - 45 60 60.5 58.2 630 195 825
-099xx 5 99 109 126 75 100 - - 96.9 92.9 1467 407 1874
77 116 138 - - 55 75 75.1 72.3 1053 308 1361
-125xx 6 125 138 188 90 125 - - 122 117 1400 500 1900
99 149 198 - - 75 100 96.6 93 1467 407 1874
-144xx 6 144 158 216 110 150 - - 141 135 1668 612 2280
125 188 250 - - 90 125 122 117 1400 500 1900
Note: The alpha ā€œPā€ in the model number stands for a decimal point in the amp rating.
Example: -2P2xxx is equivalent to 2.2 continuous output amps.