User Manual Instruction Manual

11-70
GV6000 AC Drive User Manual
Enables/disables alarm conditions that will initiate a drive alarm.
Resets all Alarm1 - 8 Code parameters (262 - 269) to zero.
A code that represents a drive alarm. The codes will appear in the order that the
alarms occur. The first code in is the first out. A time stamp is not available with
alarms.
259 Alarm Config 1
Range: See figure 11.25
Default: See figure 11.25
Access: 2 Path: Utility>Alarms
See also:
Figure 11.25 – Alarm Config 1 (259)
000000
x
000000000
10 01234567891112131415
1
=Condition True
0
=Condition False
x =Reserved
Bit #
Prechrg Actv
UnderVoltage
Power Loss
Str At PwrUp
Anlg in Loss
IntDBRes OH
Drv OL Lvl 1
Drv OL Lvl 2
Decel Inhibt
Waking
Motor Therm
In PhaseLoss
Load Loss
Ground Warn
Brk Slipped
00
xxxxxxxxxxxxx
26 161718192021222324252728293031
1
=Condition True
0
=Condition False
x =Reserved
Bit #
Prof SetHome
PTC HW
Reserved
x
261 Alarm Clear
Range: 0 = Ready
1 = Clr Alarm Que
Default: 0 = Ready
Access: 1 Path: Utility>Alarms
See also: 262 - 269
262
263
264
265
266
267
268
269
Alarm 1 Code
Alarm 2 Code
Alarm 3 Code
Alarm 4 Code
Alarm 5 Code
Alarm 6 Code
Alarm 7 Code
Alarm 8 Code
Range: 0 to 65535 [1]
Default: Read Only
Access: 1 Path: Utility>Alarms
See also: 261