User Manual Instruction Manual
11-68
GV6000 AC Drive User Manual
Enables/disables annunciation of the faults shown in figure 11.24.
Resets a fault and clears the fault queue.
Enables/disables a fault reset (clear faults) attempt from any source. This does not
apply to fault codes, which are cleared indirectly via other actions.
238 Fault Config 1
Range: See figure 11.24
Default: See figure 11.24
Access: 2 Path: Utility>Faults
See also:
Figure 11.24 – Fault Config 1 (238)
1
x
10001000
x
000
xx
10 01234567891112131415
1
=Enabled
0
=Disabled
x =Reserved
Bit #
Factory Default Bit Values
Power Loss
UnderVoltage
Motor OverLd
Shear Pin
AutRst Tries
Decel Inhibt
Motor Therm
In PhaseLoss
Load Loss
ShearPNo Acc
Out PhaseLoss
PTC HW
Reserved
Reserved
240 Fault Clear
Range: 0 = Ready
1 = Clear Faults
2 = Clr Flt Que
Default: 0 = Ready
Access: 2 Path: Utility>Faults
See also:
241 Fault Clear Mode
Range: 0 = Disabled
1 = Enabled
Default: 1 = Enabled
Access: 2 Path: Utility>Faults
See also: