Parameter Descriptions
11-65
Captures and displays the DC bus voltage of the drive at the time of the last fault.
Captures and displays Drive Status 1 bit pattern at the time of the last fault.
Captures and displays Drive Status 2 bit pattern at the time of last fault.
226 Fault Bus Volts
Range: 0.0 to Max Bus Volts [0.1 VDC]
Default: Read Only
Access: 2 Path: Utility>Diagnostics
See also: 224-230
227 Status 1 @ Fault
Range: See figure 11.20
Default: Read Only
Access: 2 Path: Utility>Diagnostics
See also: 209, 224-230
Figure 11.20 – Status 1 @ Fault (227)
0110000101110000
10 01234567891112131415
1
=Condition True
0
=Condition False
x =Reserved
Bit #
Ready
Active
Command Dir
Actual Dir
Accelerating
Decelerating
Alarm
Faulted
At Speed
Local ID 0
Local ID 1
Local ID 2
Spd Ref ID 0
Spd Ref ID 1
Spd Ref ID 2
Spd Ref ID 3
Nibble 1Nibble 2Nibble 3Nibble 4
228 Status 2 @ Fault
Range: See figure 11.21
Default: Read Only
Access: 2 Path: Utility>Diagnostics
See also: 210, 224-230
Figure 11.21 – Status 2 @ Fault (228)
00000000000000
x
0
10 01234567891112131415
1
=Condition True
0
=Condition False
x =Reserved
Bit #
Ready
Active
Running
Jogging
Stopping
DC Braking
AutoTuning
DB Active
AutoRst Ctdn
AutoRst Act
Curr Limit
Bus Freq Reg
Motor Overld
DPI at 500 k
Reserved
PTC HW