User Manual Instruction Manual

Parameter Descriptions
11-57
Important: In Dynamic Mode, changes to the parameters are not saved to nonvolatile
storage. Switching user sets restores the values last saved before
enabling dynamic mode.
Selects user set if Dyn UserSet Cnfg = xxxx xx11.
!
ATTENTION:The GV6000 can be configured to use multiple saved
parameter (user) sets. Caution must be utilized to ensure that each user
set is programmed for proper operation for the application. Recalling an
improperly programmed user set may cause rotation of the motor in an
undesired direction at unexpected speeds or may cause unpredictable
starting of the drive and motor. Failure to observe this precaution could
result in damage to equipment, severe bodily injury or loss of life.
205 Dyn UserSet Sel
Range: See figure 11.11
Default: See figure 11.11
Access: 2 Path: Utility>Drive Memory
See also:
Figure 11.11 – Dyn UsrSet Sel
!
ATTENTION:The GV6000 can be configured to use multiple saved
parameter (user) sets. Caution must be utilized to ensure that each user
set is programmed for proper operation for the application. Recalling an
improperly programmed user set may cause rotation of the motor in an
undesired direction at unexpected speeds or may cause unpredictable
starting of the drive and motor. Failure to observe this precaution could
result in damage to equipment, severe bodily injury or loss of life.
0
xx
0
xxxxxxxxxxxx
10 01234567891112131415
Bit #
Factory Default Bit Values
Dynamic Mode
Ctrl Source
Dynamic Mode
1
=Enabled
0
=Disabled
Ctrl Source
1
=[Dyn UserSet Sel]
0
=Digital Inputs
x = Reserved