Enables/disables the feature that saves the present MOP (motor-operated
potentiometer) frequency reference at power down or at stop.
Sets the rate of change of the MOP reference in response to a digital input.
Displays the present parameter access level.
The value of this parameter is not affected by a “Reset Defalts” command.
194 Save MOP Ref
Range: See figure 11.9
Default: See figure 11.9
Access: 2 Path: Utility>MOP Config
See also:
Figure 11.9 – Save MOP Ref (194)
0
xx
0
xxxxxxxxxxxx
10 01234567891112131415
1
=Save
0
=Do Not Save
x =Reserved
Bit #
Factory Default Bit Values
At Powr Down
At Stop
Nibble 1Nibble 2Nibble 3Nibble 4
195 MOP Rate
Range: 0.2 to Maximum Frequency [0.1 Hz/sec]
6.0 to Maximum Frequency [0.1 RPM/sec]
Default: 1.0 Hz/sec or 30.0 RPM/sec
Access: 2 Path: Utility>MOP Config
See also:
196 Param Access Lvl
Range: 0 = Basic
1 = Standard
2 = Advanced
Default: 0 = Basic
Access: 2 Path: Utility>Drive Memory
See also: