User Manual Instruction Manual
11-52
GV6000 AC Drive User Manual
Allows configuration of the operation of all attached OIM devices (independent of
Logic Source Sel (89)). Upper word (bits 16-31) are reserved.
At Power Down:
Inactive = Preload OIM reference with zero at power-up.
Active = Save OIM references at power down and preload them at power-up.
Manual Mode:
Inactive = Transition from Auto to Manual causes only reference to be controlled from
the requesting OIM.
Active = Transition from Auto to Manual causes reference and control (Start, Jog,
Direction, Clear Faults) to be controlled from the requesting OIM.
OIM Disable:
Inactive: OIM Start, Jog, Direction, and Clear Fault commands are functional.
Active: OIM Start, Jog, Direction, and Clear Fault commands are disabled.
Enables/disables a feature to automatically load the present auto frequency reference
value into the OIM when Manual is selected. Allows smooth speed transition from
Auto to Manual.
192 Save OIM Ref
Range: See figure 11.8
Default: See figure 11.8
Access: 2 Path: Utility>OIM Ref Config
See also:
Figure 11.8 – Save OIM Ref (192)
0
x
01
xxxxxxxxxxxx
10 01234567891112131415
Bit #
Factory Default Bit Values
At Powr Down
Manual Mode
OIM Disable
Reserved
193 Man Ref Preload
Range: 0 = Disabled
1 = Enabled
Default: 1 = Enabled
Access: 2 Path: Utility>OIM Ref Config
See also: