User Manual Instruction Manual

11-38
GV6000 AC Drive User Manual
Sets the percentage of acceleration or deceleration time that is applied to the ramp as
S Curve. Time is added; 1/2 at the beginning and 1/2 at the end of the ramp.
Selects the source for the adjustment of current limit (i.e., parameter, analog input,
etc.).
Defines the current limit value when Current Lmt Sel (147) = Cur Lim Val.
When in Adj Voltage mode, the output voltage will not be allowed the exceed this
value.
Sets the responsiveness of the current limit.
146 S Curve %
Range: 0 to 100% [0.1%]
Default: 0%
Access: 0 Path: Dynamic Control>Ramp Rates
See also: 140 - 143
147 Current Lmt Sel
Range: 0 = Curr Lim Val
1 = Analog In 1
2 = Analog In 2
Default: 0 = Cur Lim Val
Access: 2 Path: Dynamic Control>Load Limits
See also: 146, 149
148 Current Lmt Val
Range: Based on Drive Type [0.1 Amps]
Default: Rated Amps x 1.5 (Yields approximate default value)
Access: 0 Path: Dynamic Control>Load Limits
See also: 147, 149
149 Current Lmt Gain
Range: 0 to 5000 [1]
Default: 250
Access: 2 Path: Dynamic Control>Load Limits
See also: 147, 148