Selects the source of the PI reference signal. Setting this parameter to 0 = PI Setpoint
indicates PI Setpoint (127) is used.
Provides an internal fixed value for the process setpoint when PI Reference Sel (126)
is set to PI Setpoint.
126 PI Reference Sel
Range: 0 = Setpoint
1 = Analog In 1
2 = Analog In 2
3-6 = Reserved
7 = Pulse In
8 = Encoder
9 = MOP Level
10 = Master Ref
11 = Preset Spd 1
12 = Preset Spd 2
13 = Preset Spd 3
14 = Preset Spd 4
15 = Preset Spd 5
16 = Preset Spd 6
17 = Preset Spd 7
18 = Local OIM
19 = DPI Port 2
20 = DPI Port 3
21 = DPI Port 4
22 = Network
23-24 = Reserved
25 = Scale Block 1
26 = Scale Block 2
27 = Scale Block 3
28 = Scale Block 4
Default: 0 = PI Setpoint
Access: 2 Path: Speed Command>Process PI
See also: 124-138
127 PI Setpoint
Range: -/+100.00% of Maximum Process Value [0.01%]
Default: 50.00%
Access: 2 Path: Speed Command>Process PI
See also: 124-138