User Manual Instruction Manual
11-28
GV6000 AC Drive User Manual
Scales the upper value of the Trim In Select (117) selection when the source is an
analog input.
Scales the lower value of the Trim In Select (117) selection when the source is an
analog input.
Important: Parameters 121, 122, and 123 are used to enable and tune the Slip
Compensation Regulator. In order to allow the regulator to control drive
operation, Feedback Select (80) must be set to 1 = Slip Comp.
Sets the amount of compensation to drive output at motor FLA. If Autotune (61) is set
to 3 = Calculate, changes made to this parameter will not be accepted.
Value may be changed by Autotune (61) when “Encoder” is selected in Feedback
Select (80).
Figure 11.4 – Trim Out Select (118)
00000000000000
x
0
10 01234567891112131415
1
=Condition True
0
=Condition False
x =Reserved
Bit #
Ready
Active
Running
Jogging
Stopping
DC Braking
AutoTuning
DB Active
AutoRst Ctdn
AutoRst Act
Curr Limit
Bus Freq Reg
Motor Overld
DPI at 500 k
Reserved
PTC HW
119 Trim Hi
Range: -/+Maximum Speed [0.1 Hz or 1 RPM/%]
Default: 60.0 Hz
Access: 2 Path: Speed Command>Speed Trim
See also: 79, 82, 117
120 Trim Lo
Range: -/+Maximum Speed [0.1 Hz] or 1 RPM/%]
Default: 0.0 Hz
Access: 2 Path: Speed Command>Speed Trim
See also: 79, 117
121 Slip RPM @ FLA
Range: 0.0 to 1200.0 RPM [0.1 RPM]
Default: Based on Motor NP RPM
Access: 2 Path: Speed Command>Slip Comp
See also: 61, 80, 122, 123