Parameter Descriptions
11-23
Selects the source of the speed reference to the drive unless Preset Speed 1-7
(101-107) is selected.
Note that the manual reference command and input OIM Control can override the
reference control source.
93 Speed Ref B Sel
Range: 1 = Analog In 1
2 = Analog In 2
3-6 = Reserved
7 = Pulse In
8 = Encoder
9 = MOP Level
10 = Reserved
11 = Preset Spd 1
12 = Preset Spd 2
13 = Preset Spd 3
14 = Preset Spd 4
15 = Preset Spd 5
16 = Preset Spd 6
17 = Preset Spd 7
18 = Local OIM
19 = DPI Port 2
20 = DPI Port 3
21 = DPI Port 4
22 = Network
23-24 = Reserved
25 = Scale Block 1
26 = Scale Block 2
27 = Scale Block 3
28 = Scale Block 4
Default: 11 = Preset Spd 1
Access: 0 Path: Speed Command>Speed References
Speed Command> Control Src Select
See also: 2, 91-93, 101-107, 117-120, 192-194, 213, 272, 273, 361-366
!
ATTENTION:Removing and replacing the LCD OIM while the drive is
running may cause an abrupt speed change if the LCD OIM is the
selected reference source. The drive will ramp to the reference level
provided by the OIM at the rate specified in Accel Time 1 (140), Accel
Time 2 (141), Decel Time 1 (142) and Decel Time 2 (143). Be aware that
an abrupt speed change may occur depending upon the new reference
level and the rate specified in these parameters. Failure to observe this
precaution could result in bodily injury.