Software Start-Up and Ref. Manual Owner manual
1-18
GV3000/SE AC Drive Software Reference, Version 6.06
Step 5.22 Press the
▲ key until H.018, Volts/Hertz Curve Type, is displayed.
This parameter selects the type of curve
for volt/hertz regulation. See chapter 4
and step 5.24 for more information.
Step 5.23 Press the ENTER key.
The default setting is 0 for linear curve.
Step 5.24 Press the
▲ key to increase the selection value to 1 or 2, or leave it at 0.
The adjustment range is:
0 = Linear curve
1 = Optimized curve for Reliance
Electric RPM AC motors
2 = For centrifugal pump and fan motor
applications
VALUE ENTERED:
Step 5.25 Press the ENTER key to save the changed value.
After pressing ENTER, the same
parameter is displayed. You can now
move to the next parameter.