Software Start-Up and Ref. Manual Owner manual

5-6
GV3000/SE AC Drive Software Reference, Version 6.06
5.3 Accessing, Reading, and Clearing the Faults in the
Error Log
The following procedure shows how to access and clear the error log. Note that you
cannot clear a single entry from the error log. The entire log, including all the fault
codes and the day and time stamp of each fault, will be cleared simultaneously using
this procedure.
SF Self-tuning status
(Vector only)
See parameter U.009
SrL Communication
loss between
Regulator/PC/OIM
Serial port communication cable, PC
or OIM communication port setup.
Check connection cable and
communication port setup.
UAr Spurious host PC
comm interrupt
Regulator board failure. Replace Regulator board.
UbS Asymmetrical bus
charge
Bad Power Module. Contact Reliance.
Table 5.2 List of Fault Codes (Continued)
Code
Fault
Description Fault Cause Corrective Action
Step 1. Press the PROGRAM key.
The First Menu General parameters are
displayed. The PROGRAM LED will turn on.
Step 2. Press the
key until Err is displayed.
3
PROGRAM
(
PROGRAM