P.031 to P.038 Preset Speed 1 through Preset Speed 8
(continued)
The encoder loss detection diagnostic is functional only when the drive is operating as
a speed regulator (not as a torque regulator).
When the diagnostic is enabled and feedback from the encoder is not detected, a
drive fault will be logged (EL will be displayed).
If the encoder fails, loss will be detected down to 1 RPM. If only one of the quadrature
feedback wires is disconnected, loss may not be detected below 15 RPM.
Figure 4.6 Typical Preset Operation
P.039 Encoder Loss Enable
This parameter
enables the encoder
loss detection
diagnostic.
This diagnostic is
available for flux
vector control (FVC)
only.
Parameter Range:
OFF = Disable encoder loss diagnostic
ON = Enable encoder loss diagnostic
Default Setting:
OFF
Parameter Type:
Tunable
Refer also to parameters:
N/A