User Manual
3-8
GV3000/SE AC Drive Hardware Reference, Version 6.06
Standard reactors can be used on GV3000/SE drives with carrier frequency settings up to 8 kHz.
All reactors listed are UL-recognized (UL-506 File #E53094) and CSA certified (CSA File #LR29753).
Table 3.10 – Recommended Motor Lead Lengths for Reliance Inverter Duty Motors
Maximum Lead Length in Feet with
460 VAC Motor
GV3000/SE
HP Rating Filter Type
Carrier Frequency
2 kHz 4 kHz 8 kHz
1 to 2
None
500 500 500
3 to 5 500 500 500
7.5 to 10 750 500 500
15 to 20 800 500 500
25 to 60 800 500 500
75 to 100 800 500 500
125 to 150 800 500 500
200 to 400 1000 1000 1000
1 to 2
A 5% reactor/filter
at the drive.
1000 1000 1000
3 to 5 1000 1000 1000
7.5 to 10 1000 1000 1000
15 to 20 1000 1000 1000
25 to 60 1000 1000 1000
75 to 100 1000 1000 1000
125 to 150 1000 1000 1000
200 to 400 1000 1000 1000
Table 3.11 – Compatible Reactors
GV3000/SE
HP Rating
480 Volt
5% Reactor
GV3000/SE
HP Rating
480 Volt
5% Reactor
1 RL-00202
50 RL-08003
2 RL-00403
60 RL-08003
3 RL-00403
75 RL-10003
5 RL-00803
100 RL-13003
7.5 RL-01203
125 RL-16003
10 RL-01803
150 RL-20003
15 RL-02503
200 RL-25003
20 RL-03503
250 RL-32003
25 RL-03503
300 RL-40003
30 RL-04503
350 RL-50003
40 RL-05503
400 RL-50003