GV3000/SE AC Drive Hardware Reference, Version 6.06
3.1.3 Verifying the Site Provides for Recommended Air Flow Clearances
Be sure there is adequate clearance for air circulation around the drive. For best air
movement, do not mount GV3000/SE drives directly above each other. Note that no
devices are to be mounted behind the drive. This area must be kept clear of all control
and power wiring. Refer to figure 3.2 for recommended air flow clearances.
Figure 3.2 Recommended Air Flow Clearances
* If adjacent to other drives
200-400 HP
(4")
VIEW FROM TOP
1-60 HP
10 cm (4")
25 cm (10")*
25cm (10")*
10cm (4")
10cm
2 cm (0.8")
2 cm (0.8")
60-150 HP
4 cm (1.6")*
10 cm (4")
4 cm (1.6")*
10 cm (4")
(4")
10cm
OFF
ON
LRUCR
L
U
(24.0")
610 mm