GV3000/SE AC Drive ControlNet Network Communication Option Board
N10:107 DC Braking Current H.007 Tun a bl e 1 = 1%
N10:108 DC Braking Time H.008 Tun a bl e 30 = 3.0 sec
N10:109 Avoidance Freq. Enable H.009 Tu n a ble 0 = off; 1 = on
N10:110 Avoidance Freq. Midpoint 1 H.010 Tun a bl e 50 = 5.0 Hz
N10:111 Avoidance Freq. Band 1 H.011 Tun ab le 20 = 2.0 Hz
N10:112 Avoidance Freq. Midpoint 2 H.012 Tun a bl e 50 = 5.0 Hz
N10:113 Avoidance Freq. Band 2 H.013 Tun ab le 20 = 2.0 Hz
N10:114 Avoidance Freq. Midpoint 3 H.014 Tun a bl e 50 = 5.0 Hz
N10:115 Avoidance Freq. Band 3 H.015 Tun ab le 20 = 2.0 Hz
N10:116 Sync Direction H.016 Configurable 0 = off; 1 = F; 2 = r; 3 = Fr; 4 =rF
N10:117 Input Pwr/Snubber Config. H.017 Configurable 0 to 5
N10:118 Volts/Hertz Curve Type H.018 Configurable 0 to 2
N10:119 Identification Result H.019 Read Only 0 to 6
N10:120 Identification Request H.020 Configurable Note 1
N10:121 AC Line Volts H.021 Configurable 460 = 460 V
N10:122 Overfrequency Limit H.022 Configurable 900 - 90.0 Hz
N10:123
|
N10:148
Reserved Note 1
U Parameters
N10:100 Torque Reference Source U.000 Configurable 0 to 3
N10:101 Encoder PPR U.001 Configurable 0 = 512; 1 = 1024; 2 = 2048; 3 = 4096;
4 = SE
N10:102 Motor Poles U.002 Configurable 0 = 2; 1 = 4; 2 = 6; 3 = 8
N10:103 Motor Nameplate Base Freq U.003 Configurable 600 = 60.0 Hz
N10:104 Motor Nameplate Amps U.004 Configurable 100 = 10.0 A
N10:105 Motor Nameplate RPM U.005 Configurable 1785 = 1785 RPM
N10:106 Magnetizing Current U.006 Configurable 500 = 50.0%
N10:107 Motor Nameplate Volts U.007 Configurable 460 = 460 V
N10:108 Torque Self-Tune Enable U.008 Configurable Note 1
N10:109 Torque Self-Tune Result U.009 Read Only 0 to 7
N10:110 Reserved U.010 Note 1
N10:111 Reserved U.011 Note 1
N10:112 Spd. Reg. Prop. Gain U.012 Tu n a ble 500 = 5.00
N10:113 Spd. Reg. Integral Gain U.013 Tu n a ble 500 = 5.00
N10:114 Torque Reg. Prop. Gain U.014 Tu n able 40 = 0.40
Table 7.1 – File N10:X (Drive Read/Write Parameters)
File
Address Parameter Name
Parameter
Number Type Notes
Note 1: This parameter cannot be changed from the ControlNet network, or it is reserved. When writing to this parameter, use
a value of 0. When you read this parameter, you receive a value of 0.