7-2
GV3000/SE AC Drive ControlNet Network Communication Option Board
N10:26 Function Loss Response P.026 Tun a bl e 0 = IET; 1 = Coast
N10:27 Forward/Reverse Configure P.027 Tu n a ble 0 = enable; 1 = rev. disable; 2 = latch
N10:28 Speed Display Scaling P.028 Tun a bl e Units
N10:29 Elapsed Time Meter P.029 Read Only Days
N10:30 Control Bits P.030 bit 0 = Elapsed Time Reset
bit 1 = CNI Inertia Compensation
bit 2 = CNI Speed PI Limit Enable
N10:31 Preset Speed 1 P.031 Tun a bl e 50 = 5.0 Hz / 150 = 150 RPM
N10:32 Preset Speed 2 P.032 Tun a bl e 50 = 5.0 Hz / 150 = 150 RPM
N10:33 Preset Speed 3 P.033 Tun a bl e 50 = 5.0 Hz / 150 = 150 RPM
N10:34 Preset Speed 4 P.034 Tun a bl e 50 = 5.0 Hz / 150 = 150 RPM
N10:35 Preset Speed 5 P.035 Tun a bl e 50 = 5.0 Hz / 150 = 150 RPM
N10:36 Preset Speed 6 P.036 Tun a bl e 50 = 5.0 Hz / 150 = 150 RPM
N10:37 Preset Speed 7 P.037 Tun a bl e 50 = 5.0 Hz / 150 = 150 RPM
N10:38 Preset Speed 8 P.038 Tun a bl e 50 = 5.0 Hz / 150 = 150 RPM
N10:39 Encoder Loss Enable P.039 Tun a bl e 0 = off; 1 = on
N10:40 Motor Overload Enable P.040 Configurable 0 = off; 1 = on
N10:41 Motor Overload Type P.041 Configurable 0 = nC; 1 = FC
N10:42 Line Dip Ride-Through Time P.042 Configurable 1 = 0.1sec
N10:43 Fault Auto Reset Attempts P.043 Configurable 0 to 10
N10:44 Fault Auto Reset Time P.044 Configurable 8 = 8 sec
N10:45 Output Phase Loss Enable P.045 Tun a bl e 0 = off; 1 = on
N10:46 Reserved P.046 Note 1
N10:47 Carrier Frequency (kHz) P.047 Configurable 0 = 2 kHz; 1 = 4 kHz; 2 = 8 kHz
N10:48 V/Hz or Vector Regulation P.048 Configurable 0 = V/Hz; 1 = Vector
N10:49 Country Defaults P.049 Configurable 0 = USA; 1 = EUr; 2 = JPn
N10:50 Restore Defaults P.050 Note 1
N10:51 Programming Disable P.051 Tun a bl e Enter the password (26)*
N10:52 AUTO/MAN Key Disable P.052 Tun a bl e 0 = off; 1 = on
N10:53 Manual Ref. Preset Enable P.053 Tun abl e 0 = off; 1 = on
N10:54 Level Sense Start Enable P.054 Configurable 0 = off; 1 = on
N10:55 STOP/RESET Key Disable P.055 Tun a bl e 0 = off; 1 = on
N10:56 Reserved P.056 Note 1
N10:57 Reserved P.057 Note 1
* When you write to P.051, entering the password toggles disabling programming from the drive keypad. When you
read P.051, 0 = programming enabled, 1 = programming disabled.
Table 7.1 – File N10:X (Drive Read/Write Parameters)
File
Address Parameter Name
Parameter
Number Type Notes
Note 1: This parameter cannot be changed from the ControlNet network, or it is reserved. When writing to this parameter, use
a value of 0. When you read this parameter, you receive a value of 0.