5-16
AutoMax Network Communication Option Board for the GV3000/SE AC Drive
Table 5.9 – Register Assignment for Drop_3 Area (Volts/Hertz) Read/Write Registers
Register Bit Description or GV3000/SE Parameter Settings Update*
32 Motor Nameplate Volts (H.000) 1 = 1 VAC T
33 Motor Nameplate Base Frequency (H.001) 1 = 0.1 Hz T
34 Motor Nameplate Amps (H.002) 1 = 0.1 amps T
35 Torque Boost Voltage (H.003) 1 = 0.1% of nominal inverter voltage T
36 Slip Compensation (H.004) 1 = 0.01% of base frequency T
37 0 DC Braking Enable (H.005) 1 = enabled T
1 to 15 Reserved Must be 0
38 DC Braking Start Frequency (H.006) 1 = 0.1 Hz T
39 DC Braking Current (H.007) 1 = 1.0% of motor nameplate amps T
40 DC Braking Time (H.008) 1 = 0.1 seconds T
41 0 Avoidance Frequency Enable (H.009) 1 = enabled T
1 to 15 Reserved Must be 0
42 Avoidance Frequency Midpoint 1 (H.010) 1 = 0.1 Hz T
43 Avoidance Frequency Band 1 (H.011) 1 = 0.1 Hz T
44 Avoidance Frequency Midpoint 2 (H.012) 1 = 0.1 Hz T
45 Avoidance Frequency Band 2 (H.013) 1 = 0.1 Hz T
46 Avoidance Frequency Midpoint 3 (H.014) 1 = 0.1 Hz T
47 Avoidance Frequency Band 3 (H.015) 1 = 0.1 Hz T
48 Sync Direction (H.016) See drive software instruction manual C
49 Input Power/Snubber Configuration (H.017) See drive software instruction manual C
50 Volts/Hertz Curve Type (H.018) See drive software instruction manual C
51 to 52 Reserved Must be 0
53 AC Line Volts (H.021) 1 = 1 VAC C
54 Overfrequency Limit (H.022) 1 = 0.1 Hz C
55 to 63 Reserved Must be 0
*Update Times: T=350ms or less when tune/config enable is on. C=350ms or less when tune/config enable is on and the drive is stopped.