User Manual

Register Map Tables
5-15
Table 5.8 – Register Assignment for Drop_3 Area (Volts/Hertz) Read Only Registers
Register Bit Description or GV3000/SE Parameter Settings
Update
Time
0 Motor Nameplate Volts (H.000) 1 = 1 VAC 350ms
1 Motor Nameplate Base Frequency (H.001) 1 = 0.1 Hz 350ms
2 Motor Nameplate Amps (H.002) 1 = 0.1 amps 350ms
3 Torque Boost Voltage (H.003) 1 = 0.1% of nominal inverter voltage 350ms
4 Slip Compensation (H.004) 1 = 0.01% of base frequency 350ms
5 0 DC Braking Enable (H.005) 1 = enabled 350ms
1 to 15 Reserved
6 DC Braking Start Frequency (H.006) 1 = 0.1 Hz 350ms
7 DC Braking Current (H.007) 1 = 1.0% of motor nameplate amps 350ms
8 DC Braking Time (H.008) 1 = 0.1 seconds 350ms
9 0 Avoidance Frequency Enable (H.009) 1 = enabled 350ms
1 to 15 Reserved
10 Avoidance Frequency Midpoint 1 (H.010) 1 = 0.1 Hz 350ms
11 Avoidance Frequency Band 1 (H.011) 1 = 0.1 Hz 350ms
12 Avoidance Frequency Midpoint 2 (H.012) 1 = 0.1 Hz 350ms
13 Avoidance Frequency Band 2 (H.013) 1 = 0.1 Hz 350ms
14 Avoidance Frequency Midpoint 3 (H.014) 1 = 0.1 Hz 350ms
15 Avoidance Frequency Band 3 (H.015) 1 = 0.1 Hz 350ms
16 Sync Direction (H.016) See drive software instruction manual 350ms
17 Input Power/Snubber Configuration (H.017) See drive software instruction manual 350ms
18 Volts/Hertz Curve Type (H.018) See drive software instruction manual 350ms
19 Identification Result (H.019) See drive software instruction manual 350ms
20 Reserved
21 AC Line Volts (H.021) 1 = 1 VAC 350ms
22 Overfrequency Limit (H.022) 1 = 0.1 Hz 350ms
23 to 26 Reserved
27 Power Module Output Amps (P.095) 1 = 0.1 amps 350ms
28 Drive panel amps 1 = 0.1 amps 350ms
29 Drive panel volts 1 = 1 VAC 350ms
30 Reserved
31 Power Module Type (P.099) 350ms
*Update Times: 350 ms = 350ms or less.