AutoMax Network Communication Option Board for the GV3000/SE AC Drive
Table 5.6 – Register Assignment for Drop_3 Area (Vector) Read Only Registers
Register Bit Description or GV3000/SE Parameter Settings Update*
0 0 to 7 Torque Reference Source (U.000). 350ms
8 to 15 Outer Control Loop Feedback Select (U.040) 350ms
1 Encoder PPR (U.001)
0=512; 1=1024; 2=2048; 3=4096; 4=SE
350ms
2 Motor Poles (U.002) 0=2; 1=4; 2=6; 3=8 poles 350ms
3 Motor Nameplate Base Frequency (U.003) 1 = 0.1 Hz 350ms
4 Motor Nameplate Amps (U.004) 1 = 0.1 amps 350ms
5 Motor Nameplate RPM (U.005)
1 = 1 RPM
350ms
6 Magnetizing Current (U.006) 350ms
7 Motor Nameplate Volts (U.007) 1 = 1 volts 350ms
8 Torque Self-Tune Result (U.009) See drive software instruction manual 350ms
9 Reserved
10 Torque Regulator Proportional Gain (U.014) 1 = 0.01 350ms
11 Torque Regulator Integral Gain (U.015) 1 = 0.1 350ms
12 Field Weakening Start RPM (U.016) 1 = 1 RPM 350ms
13 Motor Top Speed (U.017) 1 = 1 RPM 350ms
14 AC Line Volts (U.018) 1 = 1 volts 350ms
15 Flux Current Regulator Proportional Gain (U.019) 1 = 0.01 350ms
16 Flux Current Regulator Integral Gain (U.020) 1 = 0.1 350ms
17 Rotor Time Constant (U.021) 1 = 0.001 seconds 350ms
18 Motor Nameplate Horsepower (U.022) 1 = 0.1 HP 350ms
19 Zero Speed Hold Time (U.025) 1 = 0.1 seconds 350ms
20 SVC Slip Adjust (U.030) 1 = 0.01 350ms
21 0 to 7 SVC Sync Direction (U.031) See drive software instruction manual 350ms
8 to 15 Outer Control Loop Lead/Lag Select (U.041) 0 = bypass; 1 = lead/lag; 2 = lag/lead 350ms
22 SVC Flux Current Regulator Gain (U.032) 1 = 1 rad/s 350ms
23 Outer Control Loop Lead/Lag Low Frequency (U.042) 1 = 0.01 rad/s 350ms
24 Outer Control Loop Lead/Lag Ratio (U.043) 1 = 1 350ms
25 Outer Control Loop Reference Gain (U.044) 1 = 0.001 350ms
*Update Times: 350 ms = 350ms or less.