Register Map Tables
5-9
19 Configurable Booleans (read)
0 Motor Overload Enable (P.040) 1 = enabled 350ms
1 Level Sense Start Enable (P.054) 1 = enabled 350ms
2 Low DC Bus Fault Avoidance Enable (SVC only) (U.023) 1 = enabled 350ms
3 High DC Bus Fault Avoidance Enable (U.024). Vector only. 1 = enabled 350ms
4 Outer Control Loop Proportional Trim Enable (U.048) 1 = enabled 350ms
5 to 15 Reserved
20 Motor Overload Type (P.041) 0 = nC; 1 = FC 350ms
21 Line Dip Ride-Through Time (P.042). V/Hz only. 1 = 0.1 seconds 350ms
22 Fault Auto Reset Attempts (P.043) 0 = disable auto reset 350ms
23 Fault Auto Reset Time (P.044) 1 = 1 second 350ms
24 Tunable Booleans (Read)
0 Encoder Loss Enable (P.039) 1 = enabled 350ms
1 Output Phase Loss Enable (P.045) 1 = enabled 350ms
2 Manual Reference Preset Enable (P.053) 0 = do not preset the manual reference
1 = enable (see software manual)
350ms
3
AUTO/MAN Key Disable (P.052) 1 = key disabled 350ms
4
STOP/RESET Key Disable (P.055) 1 = key disabled 350ms
5 to 15 Reserved
25 Current Compounding Gain (U.026). Vector only. 1 = 0.001 350ms
26 Carrier Frequency (kHz) (P.047) 0 = 2kHz; 1 = 4kHz; 2 = 8kHz 350ms
27 Volts/Hertz or Vector Regulation (P.048) 0 = V/Hz; 1 = Vector 350ms
28 Country Defaults (P.049) 0 = USA; 1 = EUr; 2 = JPn 350ms
29 Inertia Compensation Gain (U.027). Vector only. 1 = 0.001 350ms
30 Losses Compensation Gain (U.028). Vector only. 1 = 0.001 350ms
31 Option Port: Type and Version (P.065) 2103 = AutoMax Network V1.03 350ms
Table 5.4 – Register Assignment for Drop_2 Area Read Only Registers (Continued)
Register Bit Description or GV3000/SE Parameter Settings Update*
*Update Times: 5 ms = 5 ms. 350 ms = 350ms or less.