User Manual

5-4
AutoMax Network Communication Option Board for the GV3000/SE AC Drive
13 (con’t.) 13 Analog input signal loss (AIn) 350ms
14 Reserved
15 Fatal system error 350ms
14 0 to 7 Number of error log entries 350ms
8 Parameter processing error flag 350ms
9 to 15 Reserved
15 0 to 7 Error log entry (second most recent error) 350ms
8 to 15 Error log entry (most recent error) 350ms
16 Control Source (P.000) 0 = Front-panel (Local); 1 = Terminal
strip; 2 = Option Port (Network master)
3 = Serial Port (PC-HOST)
350ms
17 Accel Time 1 (RAMP 1) (P.001) 1 = 0.1 seconds 350ms
18 Decel Time (RAMP 1) (P.002) 1 = 0.1 seconds 350ms
19 Minimum Speed (P.003) V/Hz: 1 = 0.1 Hz. Vector: 1 = 1 RPM 350ms
20 Maximum Speed (P.004) V/Hz: 1 = 0.1 Hz. Vector: 1 = 1 RPM 350ms
21 Current Limit (P.005) 1 = 1% 350ms
22 Trim Gain Percentage (P.015) 1 = 0.1% 350ms
23 Draw Gain Percentage (P.016) 1 = 0.1% 350ms
24 Speed Regulator Proportional Gain (U.012). Vector only. 1 = 0.01 350ms
25 Speed Regulator Integral Gain (U.013). Vector only. 1 = 0.01 350ms
26 Status word 2
0 Torque or speed regulation. Vector only. 1 = speed 5ms
1 Auto or manual (local) reference selected 1 = manual 5ms
2 Outer control loop enabled 1 = enabled 5ms
3 to 15 Reserved
27 Elapsed Time Meter (P.029) days 350ms
28 Network Connection Type (P.061) 0 = basic; 1 = full 350ms
29 Option Port: Communication Loss Response (P.062) 350ms
30 0 to 7 Option Port: Network Reference Source (P.063) 0 = direct; 1 to 8 = broadcast 1 to 8 350ms
8 to 15 Option Port: Network Trim Reference Source (P.064) 0 = direct; 1 to 8 = broadcast 1 to 8 350ms
31 Software Version Number (P.098) 601 = Version 6.01 350ms
Table 5.2 – Register Assignment for Drop_1 Area Read Only Registers (Continued)
Register Bit Description or GV3000/SE Parameter Settings Update*
*Update Times: 5 ms = 5 ms. 350 ms = 350ms or less.