User Manual
7-17
Wiring the Regulator Board Terminal Strip
Table 7.8 – Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
28
29
30
31
Description
Normally-Closed Contact
(Form B)
Normally-Closed Contact
Common (Form B)
Normally-Open Contact
(Form A)
Normally-Open Contact
Common (Form A)
Parameters/Wiring Connections
Both Form A and Form B contacts are rated for 250 VAC/30 VDC at
5 amps resistive or 2 amps inductive load.
The following parameter must be set:
P.013: Output Relay Configuration
Note that depending on the setting of parameter P.013, the
relay coil will energize (the normally-open contact will close and the
normally-closed contact will open). Refer to the GV3000/SE
Software Start-Up and Reference manual for more information.
Wiring the Output Status Relays
28 29 30 31
N.C.
COM
N.O.
COM
USER SUPPLIED
DEVICE
PARAMETER P.013 SELECTS OUTPUT
INDICATION