Hardware Ref, Installation, and Troubleshooting Owner's manual

3-2
GV3000/SE AC Bookshelf Drive Hardware Reference, Version 6.06
Do not install the drive above 1000 meters (3300 feet) without derating output
power. For every 91.4 meters (300 feet) above 1000 meters (3300 feet), derate the
output current 1%.
Verify that the drive location will meet the environmental conditions specified in table
3.1.
Table 3.1 Environmental Conditions
Condition Specification
Operating Temperature (Ambient) 0° to +40°C (32° to 104°F) coolant air
inlet temperature at heatsink
Derating factor at 45°C (113°F)
ambient: Output current by 7.5%
Derating factor at 50°C (122°F)
ambient: Output current by 15%
Storage Temperature (Ambient) -25°C to +55°C (-77° to +131°F)
Transportation Temperature (Ambient) -25°C to +70°C (-77° to +158°F)
(+70°C (+158°F) during max. 24 hrs)
Humidity Maximum: 50% at 40°C (104°F)
unlimited
Maximum: 90% at 20°C (68°F) during
maximum 30 days/year
75% average
No condensation