Software Start-Up and Ref. Owner manual
Table Of Contents
- GV3000/SE AC General Purpose (V/Hz) and Vector Duty Drive, 1 - 20 HP, 230V AC Software Start-Up and Reference Manual D2-3387-5
- Important User Information
- Document Update
- Summary of Changes
- Table of Contents
- List of Figures
- List of Tables
- Preface
- Chapter 1 - Starting Up the Drive for Volts/Hertz Regulation
- Chapter 2 - Starting Up the Drive for Vector Regulation
- Chapter 3 - Using the Keypad/Display To Program, Monitor, and Control the Drive
- Chapter 4 - Programming Reference
- Chapter 5 - Troubleshooting the Drive Using Error Codes
- Appendix A - Alphabetical Listing of Parameters
- Appendix B - Record of User Parameter Settings
- Appendix C - Power Module-Dependent Parameter Default Values (230 V Series)
- Appendix D - Default Parameter Settings
- Appendix E - Configuring the Digital Inputs When the RMI Board Is Installed in the Drive
- Appendix F - Using the Terminal Strip Analog Input
- Appendix G - Drive Regulation Overview
- Back Cover / Publication D2-3387-5 July 2013

2-20
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Step 6.17 Press the £ key to increase the motor nameplate base frequency or
the ¥ key to decrease the motor nameplate base frequency.
The adjustment range is:
15.0 Hz to 120.0 Hz
VALUE ENTERED:
Step 6.18 Press the ENTER key to save the changed value.
After pressing ENTER, the same parameter
is displayed. You can now move to the next
parameter.
AUTO
MAN
Forward
Reverse
PROGRAM
RUN
JOG
STOP
RESET
START
ENTER
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
Step 6.19 Press the £ key to display U.004, Motor Nameplate Amps.
ATTENTION: This parameter setting must not exceed the rated amps
found on the motor nameplate. Overcurrent or excess heating of the
motor could result if this is not the case. Failure to observe this
precaution could result in damage to, or destruction of, the equipment.
This parameter is the Motor Nameplate
Rated Amps and is taken from the motor
nameplate.
!
AUTO
MAN
Forward
Reverse
PROGRAM
RUN
JOG
STOP
RESET
START
ENTER
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM