Software Start-Up and Ref. Owner manual
Table Of Contents
- GV3000/SE AC General Purpose (V/Hz) and Vector Duty Drive, 1 - 20 HP, 230V AC Software Start-Up and Reference Manual D2-3387-5
- Important User Information
- Document Update
- Summary of Changes
- Table of Contents
- List of Figures
- List of Tables
- Preface
- Chapter 1 - Starting Up the Drive for Volts/Hertz Regulation
- Chapter 2 - Starting Up the Drive for Vector Regulation
- Chapter 3 - Using the Keypad/Display To Program, Monitor, and Control the Drive
- Chapter 4 - Programming Reference
- Chapter 5 - Troubleshooting the Drive Using Error Codes
- Appendix A - Alphabetical Listing of Parameters
- Appendix B - Record of User Parameter Settings
- Appendix C - Power Module-Dependent Parameter Default Values (230 V Series)
- Appendix D - Default Parameter Settings
- Appendix E - Configuring the Digital Inputs When the RMI Board Is Installed in the Drive
- Appendix F - Using the Terminal Strip Analog Input
- Appendix G - Drive Regulation Overview
- Back Cover / Publication D2-3387-5 July 2013

E-2
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
8 Presets
Analog ref and 7 presets
4 Presets
Analog ref and 3 presets
P.007 Options
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
9 =
10 =
11 =
12 =
DIGIN 6
FWD/REV
Not used
Not used
Not used
Not used
Not used
Not used
Not used
FWD/REV
Not used
Not used
Not used
Not used
DIGIN 7
RAMP 1/2
FWD/REV
FWD/REV
RAMP 1/2
Not used
Not used
Not used
Not used
TRQ/SPD
TRQ/SPD
TRQ/SPD
TRQ/SPD
Not used
DIGIN 8
REM/LOC
RAMP 1/2
REM/LOC
REM/LOC
FWD/REV
RAMP 1/2
REM/LOC
Not used
REM/LOC
REM/LOC
FWD/REV
RAMP 1/2
TRQ/SPD
P.008 Options
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
DIGIN 6
Not used
MOP “
2 Presets
Analog ref and
1 preset
DIGIN 7
Not used
MOP «
Not used
Not used
DIGIN 8
Not used
Not used
Not used
Not used
Not used
Not used
Summary of Options for P.007, P.008, and r.030
r.030 Options
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
RMI DIGIN 2
A/F
A/F
MOP “
MOP “
2 Presets
2 Presets
4 Presets
4 Presets
8 Presets
RMI DIGIN 3
Aux 2
Aux 2
MOP «
MOP «
Aux 2
Aux 2
4 Presets
4 Presets
8 Presets
RMI DIGIN 4
Aux 1
PI Enable
Aux 1
PI Enable
Aux 1
PI Enable
Aux 1
PI Enable
8 Presets
RMI DIGIN 1
Ref 1/2
Ref 1/2
Ref 1/2
Ref 1/2
Ref 1/2
Ref 1/2
Ref 1/2
Ref 1/2
Ref 1/2
Option Comparison Tables
If P.007 =
0
1
2
3
4
5
6
7
8
9
10
11
12
Acceptable
P.008
Values
0
0, 2, 5
0, 2, 5
0, 2, 5
0-3, 5, 6
0-3, 5, 6
0-3, 5, 6
0-7 (all)
0
0, 2, 5
0, 2, 5
0, 2, 5
0-3, 5, 6
If r.030 =
0
1
2
3
4
5
6
7
8
Acceptable
P.008
Values
0-6 (all)
0-6 (all)
0, 2-6
0, 2-6
0, 1
0, 1
0, 1
0, 1
0, 1
If P.008 =
0
1
2
3
4
5
6
7
Acceptable
P.007
Values
0-12 (all)
4-7, 12
1-7, 9-12
4-7, 12
7
1-7, 9-12
4-7, 12
7
If P.008 =
0
1
2
3
4
5
6
7
Acceptable
r.030
Values
0-8 (all)
0, 1, 4-8
0-3
0-3
0-3
0-3
0-3
0-3