Software Start-Up and Ref. Owner manual
Table Of Contents
- GV3000/SE AC General Purpose (V/Hz) and Vector Duty Drive, 1 - 20 HP, 230V AC Software Start-Up and Reference Manual D2-3387-5
- Important User Information
- Document Update
- Summary of Changes
- Table of Contents
- List of Figures
- List of Tables
- Preface
- Chapter 1 - Starting Up the Drive for Volts/Hertz Regulation
- Chapter 2 - Starting Up the Drive for Vector Regulation
- Chapter 3 - Using the Keypad/Display To Program, Monitor, and Control the Drive
- Chapter 4 - Programming Reference
- Chapter 5 - Troubleshooting the Drive Using Error Codes
- Appendix A - Alphabetical Listing of Parameters
- Appendix B - Record of User Parameter Settings
- Appendix C - Power Module-Dependent Parameter Default Values (230 V Series)
- Appendix D - Default Parameter Settings
- Appendix E - Configuring the Digital Inputs When the RMI Board Is Installed in the Drive
- Appendix F - Using the Terminal Strip Analog Input
- Appendix G - Drive Regulation Overview
- Back Cover / Publication D2-3387-5 July 2013

4-57
Programming Reference
4.6.3 Second Menu V/Hz Parameter Descriptions (H.000 to H.022)
H.000 Motor Nameplate Base Volts
This parameter
identifies the motor
nominal voltage as it
appears on the motor
nameplate.
Parameter Range: 100 VAC to 345 VAC
Default Setting: 230 VAC
Parameter Type: Configurable
Refer also to parameters: N/A
H.001 Motor Nameplate Base Frequency
This parameter
configures the V/Hz
ratio.
Parameter Range: 30.0 Hz to 200.0 Hz
Default Setting: 60.0 Hz
Parameter Type: Configurable
Refer also to parameters: H.003 Torque Boost Voltage
H.018 Volts/Hertz Curve Type
Base frequency is the frequency at which the output voltage reaches Motor
Nameplate Voltage (H.000). Below base frequency, the output voltage varies with
output frequency according to the V/Hz adjustment in parameter H.018 (Volts/Hertz
Curve Type). Above base frequency, output voltage is held constant as frequency
increases (constant horsepower range).
The V/Hz ratio is affected by the selection of Volts/Hertz Curve Type in H.018 and
the setting of Torque Boost Voltage in H.003. See figure 4.10.
Figure 4.10 – Volts/Hertz Ratio
100
30
H.001
Maximum
V/Hz
Minimum
V/Hz
Motor
Voltage,
(H.000)
(volts)
Output Frequency
(Hz)